R3-RS8
P. 3 / 3
EM-8365 Rev.3
■
CONNECTION DIAGRAM
M-SYSTEM WARRANTY
M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such
product was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System's sole liability, and purchaser's exclusive remedies,
under this warranty are, at M-System's option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this warranty. To
submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR
SPECIAL DAMAGES OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: info@m-system.co.jp
WIRING INSTRUCTIONS
■
SOLDERLESS TERMINAL mm (inch)
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable. Solderless
terminals with insulation sleeve do not fit. Applicable wire
size: 0.3 – 0.5 mm
2
3.2 (.13) dia.
4 min.
(.16)
12 (.47) max.
6 max.
(.24)
3 (.12) max.
INPUT 1
1
2
A
B
B
RTD
3
INPUT 2
4
5
A
B
B
RTD
6
INPUT 3
7
8
A
B
B
RTD
9
INPUT 4
10
11
A
B
B
RTD
12
INPUT 5
15
16
A
B
B
RTD
17
INPUT 6
18
19
A
B
B
RTD
20
INPUT 7
21
22
A
B
B
RTD
23
INPUT 8
24
25
A
B
B
RTD
26
BUS CONNECTOR
INTERNAL POWER
BUS A
BUS B
*
*
For dual redundant communication.
• Unused Input Channels
Close across the unused input terminals with a resistor as
shown below and set the DIP switch for an RTD.
The resistance value must match the RTD type (100
Ω
for
Pt 100, 50
Ω
for Pt 50).
Unused channels left open are equal to the burnout, which
turns the red ERR LED on and sets a burnout flag at the
PLC or the host device.
Unused channels can be specified and set so on the PC
Configurator Software (model: R3CON) without needing to
connect resistors at the field terminals.
1
2
INPUT 1
4
5
INPUT 2
7
8
INPUT 3
10
11
INPUT 4
3
6
9
12
15
16
INPUT 5
17
18
19
INPUT 6
20
21
22
INPUT 7
23
24
25
INPUT 8
26