R3-TC2
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8468 Rev.3 P. 11 / 37
■
SETTING EXAMPLE 3: SWITCHING SETPOINT VALUE BY EVENT INPUT
The Controller has two discrete inputs for event control input.
At the maximum of four sets of temperature setpoints and PID parameters can be predefined and stored in the ‘banks.’ The
external event input can be used to switch among these banks.
In this example, the Controller is set according to the example 1 for the setpoint 40.0°C. By using banks, an additional setting
to switch the setpoint to 50.0°C by an event input is created.
(1) Connect a switch to the discrete input 1 as shown below.
R3-TC2
Di 1
(2) Go to the setting items tree and change the following parameters.
SETTING ITEMS TREE
PARAMETER
SELECTION
Loop 1, Bank 1
SP (setpoint value)
50.0
Event input
Event input 1 function assignment
Loop 1, Bank bit 0
(3) Click Auto-tuning button located below the trend graph to show the Auto-tuning dialog box. Choose Bank 1 and click OK.
The Controller go through auto-tuning and then starts control operations.
Now the setting is complete to switch the temperature setpoint to 50.0°C with the switch closed (ON) and to 40.0°C with the
same opened (OFF).