R3-TC2
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8468 Rev.3 P. 28 / 37
BANK
The Controller has four sets of banks per loop. Temperature setpoint and PID and other parameters can be stored and
switched easily during operation by an external event input (Di) or via Modbus communication.
Bank 0 is used when there is no bank switching.
■
SP (SETPOINT VALUE)
Specify local SP.
CAUTION
Local SP bank is saved in the nonvolatile memory of the device.
If the SP bank is changed frequently during operation, the memory may reach its limit of writing, approx.
106 cycles in a short time.
Use the ‘Setpoint Value Setting’ for frequent changes.
[Bank 0]
ADDRESS
PARAMETER
RANGE
DEFAULT
+1152
Loop 1, SP (setpoint value)
-3200.0 to +3200.0
(decimal by input 1/2 decimal setting)
25.0
+1792
Loop 2, SP (setpoint value)
[Bank 1]
ADDRESS
PARAMETER
RANGE
DEFAULT
+1312
Loop 1, SP (setpoint value)
-3200.0 to +3200.0
(decimal by input 1/2 decimal setting)
25.0
+1856
Loop 2, SP (setpoint value)
[Bank 2]
ADDRESS
PARAMETER
RANGE
DEFAULT
+1472
Loop 1, SP (setpoint value)
-3200.0 to +3200.0
(decimal by input 1/2 decimal setting)
25.0
+1920
Loop 2, SP (setpoint value)
[Bank 3]
ADDRESS
PARAMETER
RANGE
DEFAULT
+1632
Loop 1, SP (setpoint value)
-3200.0 to +3200.0
(decimal by input 1/2 decimal setting)
25.0
+1984
Loop 2, SP (setpoint value)
■
SP RAMP FALL RATE / SP RAMP RISE RATE
SP can be changed gradually in specified ramp rates when a new SP value is applied. SP ramp fall rate is applied with a
decreasing SP, while SP rise rate is with an increasing SP.
The SP is instantly switched to a new value when ‘0.0’ is set.
The setting is valid for all SP value changes except at STOP status and in error status.
[Bank 0]
ADDRESS
PARAMETER
RANGE
DEFAULT
+1153
Loop 1, SP ramp fall rate
0.0 to 3200.0 per second
(decimal by input 1 decimal setting)
0.0
+1154
Loop 1, SP ramp rise rate
+1793
Loop 2, SP ramp fall rate
0.0 to 3200.0 per second
(decimal by input 2 decimal setting)
0.0
+1794
Loop 2, SP ramp rise rate
[Bank 1]
ADDRESS
PARAMETER
RANGE
DEFAULT
+1313
Loop 1, SP ramp fall rate
0.0 to 3200.0 per second
(decimal by input 1 decimal setting)
0.0
+1314
Loop 1, SP ramp rise rate
+1857
Loop 2, SP ramp fall rate
0.0 to 3200.0 per second
(decimal by input 2 decimal setting)
0.0
+1858
Loop 2, SP ramp rise rate
[Bank 2]
ADDRESS
PARAMETER
RANGE
DEFAULT
+1473
Loop 1, SP ramp fall rate
0.0 to 3200.0 per second
(decimal by input 1 decimal setting)
0.0
+1474
Loop 1, SP ramp rise rate
+1921
Loop 2, SP ramp fall rate
0.0 to 3200.0 per second
(decimal by input 2 decimal setting)
0.0
+1922
Loop 2, SP ramp rise rate
[Bank 3]
ADDRESS
PARAMETER
RANGE
DEFAULT
+1633
Loop 1, SP ramp fall rate
0.0 to 3200.0 per second
(decimal by input 1 decimal setting)
0.0
+1634
Loop 1, SP ramp rise rate
+1985
Loop 2, SP ramp fall rate
0.0 to 3200.0 per second
(decimal by input 2 decimal setting)
0.0
+1986
Loop 2, SP ramp rise rate