R3-TC2
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8468 Rev.3 P. 16 / 37
UNIVERSAL INPUT
The Controller has two universal inputs (universal input 1, universal input 2) which can be assigned independently for tem-
perature inputs. In addition to RTD and thermocouples, resistor, DC and potentiometer inputs are also usable. The resistor,
DC and potentiometer input is scaled into a temperature range.
Universal input 1 is usually assigned as PV input signal for loop 1, while universal input 2 is for loop 2. Universal input 2
signal can be cascaded into the loop 1 SP.
• DC Voltage (-10 – +10V DC)
• DC Current (0 – 20mA DC)
CJC
SENSOR
+
––
INPUT
• DC Voltage (-1000 – +1000mV DC)
• Thermocouple
• RTD / Resistor (3-wire)
Universal Input 1
• Potentiometer
comp. leadwire
A
B
B
• RTD / Resistor (2-wire)
A
B
max.
min.
Universal Input 2
Loop 1
Loop 2
■
INPUT TYPE
ADDRESS
PARAMETER
RANGE
DEFAULT
+128
Universal input 1, Input type
See the table below.
10
+384
Universal input 2, Input type
SET VALUE
PARAMETER
SET VALUE
PARAMETER
0
DC 0 − 20mA
20
RTD Ni 508.4Ω
1
DC -1000 − +1000mV
22
RTD Cu 10
2
DC -10 − +10V
24
TC (PR)
3
POT 0 − 4000Ω
25
TC K
4
POT 0 − 2500Ω
26
TC E
5
POT 0 − 1200Ω
27
TC J
6
POT 0 − 600Ω
28
TC T
7
POT 0 − 300Ω
29
TC B
8
POT 0 − 150Ω
30
TC R
9
Resistor 0 − 4000Ω
31
TC S
10
RTD Pt 100
32
TC C
14
RTD Pt 500
33
TC N
15
RTD Pt 1000
34
TC U
16
RTD Pt 50Ω
35
TC L
17
RTD JPt 100
36
TC P