COUNT RESET
There are two different ways to reset count value.
■
COUNT RESET WITH RESET SIGNAL
With the configurator software (model: R30CFG), enable the external reset input setting. The count reset signal becomes
enabled.
One pulse supplied at the Count reset input terminal will be recognized as a reset signal.
1) ERR LED turns on (red color) when the reset signal is received.
2) In 1 second, the module starts resetting its counter.
3) After 1 second, ERR LED turns back to the state before the reset signal has been received.
Note: Reset signals received while the module is processing (1) through (3) are ignored. Even when the count overflow set value is 1,
the counter is reset to 0.
■
COUNT RESET FROM HOST PC/PLC
Refer to “COUNTER SETTING FROM HOST PC/PLC” section hereafter.