WIRING INSTRUCTIONS

 

TIGHTENING TORQUE

Separable screw terminal wiring screw: 0.5 N·m
Separable screw terminal fixing screw: 0.5 N·m

 

SOLDERLESS TERMINAL  unit: mm (inch)

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.  Solder-
less terminals with insulation sleeve do not fit.  
Applicable wire size: 0.25 to 0.75 mm

2

Recommended manufacturer: Japan Solderless Terminal
MFG. Co., Ltd., Nichifu Co., Ltd.

3.2 (.13) dia.

12 (.47) max.

6 max

.

(.24)

3 (.12) max.

 

HOW TO REMOVE SEPARABLE SCREW TERMINAL

The terminal block is separable in two pieces.  Evenly loos-
en two screws on top and bottom of the terminal block to 
separate.

PC CONFIGURATOR

The following parameter items can be set with using PC 
Configurator Software (model: R30CFG).
Refer to the users manual for the R30CFG for detailed op-
eration of the software program.

 

CHANNEL INDIVIDUAL SETTING

PARAMETER

SETTING RANGE

DEFAULT
SETTING

Max no. of totalized 
pulse

1 – 4,294,967,295

4,294,967,295

Count at overflow 
(value to which the 
count returns)


1

0

Preset value

0 – Max no. of total-
ized pulse 

0

 

CHANNEL BATCH SETTING

PARAMETER

SETTING RANGE

DEFAULT
SETTING

Count pulse edge

Falling edge (DI-ON)/
Rising edge (DI-OFF)

Falling edge 
(DI-ON)

External reset 
pulse edge to detect

Falling edge (DI-ON)/
Rising edge (DI-OFF)

Falling edge 
(DI-ON)

External reset 
detection

Disable
Enable

Disable

Reset/preset from 
host PC/PLC

Disable
Enable

Disable

Simulate input

Normal input
Simulate input

Normal input

Summary of Contents for R30PA2

Page 1: ...ore you remove the terminal block or mount it turn off input signals for safety HOT SWAPPABLE MODULES It is possible to replace a module with the power supplied provided that the module is replaced wi...

Page 2: ...ernal bus operates normally ON when an internal bus error occurs ON during reset preset processing approx 1 sec Input Status Indicator Green 1 2 Totalized pulse input ON LED On OFF LED Off R Reset inp...

Page 3: ...mes enabled One pulse supplied at the Count reset input terminal will be recognized as a reset signal 1 ERR LED turns on red color when the reset signal is received 2 In 1 second the module starts res...

Page 4: ...ut data from host PC PLC As the bits to preset the totalized value of each channel are allocated in n 1 word by changing the bits from 0 to 1 the preset values are reflected to the totalized value dat...

Page 5: ...slot is vacant blank data is sent or received to from the PLC etc PWR COM I O1 I O n HOW TO MOUNT THE MODULE 1 Engage the positioning guide of the module with the In stallation Base 2 Pivot the module...

Page 6: ...unit mm inch 110 4 33 25 98 98 3 86 20 M3 SCREW 6 24 CONNECTION DIAGRAM 1 11 2 9 12 19 10 20 PI1 C1 PI2 C2 10 20 11 1 PNP Connection RST RST V V V V PI1 C1 12 2 PI2 C2 19 9 RST RST PI1 C1 PI2 C2 RST R...

Page 7: ...in two pieces Evenly loos en two screws on top and bottom of the terminal block to separate PC CONFIGURATOR The following parameter items can be set with using PC Configurator Software model R30CFG R...

Reviews: