background image

R30TS4

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: info@m-system.co.jp

EM-9002  Rev.2  P. 2 / 5

COMPONENT IDENTIFICATION

RUN

ERR

RUN LED

Input Terminal Block

ERR LED

■ 

FRONT VIEW

■ 

BOTTOM VIEW

■ 

SIDE VIEW

Lock Tab

Base Fixing Screw

Specifications

Positioning Guide

Terminal Cover

Terminal Fixing Screw

CJC Sensor (CJM x 4)

 

STATUS INDICATOR LED

ID

COLOR

FUNCTION

RUN

Green

ON while network module operates normally
OFF in network module error

ERR

Red

OFF when input circuit and internal bus operate normally
Blinks in 1 sec. cycles when burnout is detected or with input value error (becomes less than the lower 
limit or exceeds the upper limit of usable range).
Blinks in 400 msec. cycles with input circuit error (AD converter response failure). 
ON with internal bus error

 

TERMINAL ASSIGNMENTS

11

+CJ1

12

NC

13

+CJ2

14

NC

15

NC

16

+CJ3

17

NC

18

+CJ4

19

NC

20

NC

1

+IN1

2

COM1

3

+IN2

4

COM2

5

NC

6

+IN3

7

COM3

8

+IN4

9

COM4

10

NC

NO.

ID

FUNCTION

NO.

ID

FUNCTION

1

+IN1

T/C 1

11

+CJ1

CJC 1

2

COM1 Common 1

12

NC

No connection

3

+IN2

T/C 2

13

+CJ2

CJC 2

4

COM2 Common 2

14

NC

No connection

5

NC

No connection

15

NC

No connection

6

+IN3

T/C 3

16

+CJ3

CJC 3

7

COM3 Common 3

17

NC

No connection

8

+IN4

T/C 4

18

+CJ4

CJC 4

9

COM4 Common 4

19

NC

No connection

10

NC

No connection

20

NC

No connection