EM-7787  Rev.7  P. 5 / 9

CHECKING ETHERNET CONNECTION

 

IP ADDRESS

The R6-NE1 does not support BootP Table Software.  The IP Address and Subnet Mask can be configured using the R6CON 
Configurator Software.
The Modbus/TCP Port No. is fixed at 502.

 

DATA ALLOCATION MODE

The Data Allocation Mode is usually set to ‘2’ with the side DIP switches.  Setting ‘1’ is used only when all the I/O modules on 
the base are for Data Allocation Mode 1.  This setting affects analog I/O data allocations.

 

CHECK WIRING

Connect an Ethernet cable to the front RJ-45 connector.

 

CHECK LED

When wiring is correct, LINK and LINK10, or LINK and LINK100 are turned on.
When the module is receiving or sending data, LINK10 or LINK100 blinks.*
* LEDs are turned ON for firmware version V2.02 or later.

 

CHECK R6-NE1 CONNECTION

Enter “ping command” on the Windows MS-DOS as follows:

    C:¥WINDOWS>ping ***.***.***.***
    (***.***.***.***: Enter IP address in decimal.)

    ping ***.***.***.*** with 32 bytes of data:
    Reply from ***.***.***.*** : bytes=32 time<10ms TTL=64
    Reply from ***.***.***.*** : bytes=32 time<10ms TTL=64
    Reply from ***.***.***.*** : bytes=32 time<10ms TTL=64
    Reply from ***.***.***.*** : bytes=32 time<10ms TTL=64

    Ping statistics for ***.***.***.***
    Packets:Sent=4,Received=4,Lost=0(0% loss)

Replies in case of normal connection are as shown above.  If the connection cannot be established normally due to e.g. wrong 
IP address, other replies such as ‘timeout’ will be received.

 

CHECK CONNECTION TO THE APPLICATION SOFTWARE

Check Point 1: LINK LEDs

When normal connection is established, the front LINK and LINK10 or LINK100 are turned on regardless of data sending/
receiving status.  Check power supply to the switch/hub in case that these LEDs are not on.

Check Point 2: RUN Indicator LED

With the side DIP SW3 is set to OFF, a green LED turns on at the RUN Indicator LED in normal data sending/receiving.

Check Point 3: Sending/Receiving Indicators

With the side DIP SW3 is set to ON, a red LED turns on at the RUN Indicator LED in data receiving, and a red LED turns 
on at the ERR Indicator LED in data sending.  In normal operating conditions, these LEDs may seem to blink at once due to 
the high speed transmission.

Summary of Contents for R6-NE1

Page 1: ...tem The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure the CE conform ity HOT INSERTION REMOVAL OF MODULES It is possible...

Page 2: ...to use the second channel of analog I O modules choose the Mode 2 The 2nd channel cannot be sent re ceived in the Mode 1 See COMPONENT IDENTIFICATION NETWORK SLOTS ON THE BASE Mount the Network Modul...

Page 3: ...smitting ON Blank OFF Note Be sure to set unused SW4 through 8 to OFF ETHERNET INDICATORS ID COLOR FUNCTION LINK Red ON at LINK DPLX Red ON with full duplex communication LINK10 Red ON with 10 Mbps co...

Page 4: ...info m system co jp EM 7787 Rev 7 P 4 9 TERMINAL CONNECTIONS Connect the unit as in the diagram below EXTERNAL DIMENSIONS unit mm inch 90 3 54 5 6 22 90 3 54 LOCKING CLAMP POSITIONING GUIDE 18 71 CON...

Page 5: ...er IP address in decimal ping with 32 bytes of data Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64...

Page 6: ...and a field of event bytes 13 Program Controller 14 Poll Controller 15 Force Multiple Coils X Digital output from the slave read write 16 Preset Multiple Registers X General purpose register within th...

Page 7: ...address 1 Ai 1 INT 3 Module address 2 Ai 1 INT 4 Module address 3 Ai 1 INT 16 Module address 15 Ai 1 INT 17 18 Module address 0 Ai 1 Float 19 20 Module address 1 Ai 1 Float 21 22 Module address 2 Ai...

Page 8: ...0 0 Internal Communication Counter Every Internal Communication Cycle Adds 1 CHANNEL STATUS Channel Status shows the I O module s data error Input overrange 15 or 115 of Input modules except R6x TSx a...

Page 9: ...verted into 0 to 10000 binary With C temperature unit raw data is multiplied by 10 For example 25 5 C is converted into 255 With F temperature unit the integer section of raw data is directly converte...

Reviews: