ACTIVE MODULE MAP

Indicates the slots where I/O modules are mounted.  When the module is mounted, the corresponding bit turns to “1.”

257

272

Module address 0
Module address 1
Module address 2

Module address 15

 

STATUS

Communication status data.  When one or more I/O modules are mounted on the base, the corresponding bit turns to “0.”

273

288

“0”
“0”
“0”
“0”
I/O Module Found (0 : I/O module(s) found, 1 : No I/O module found)
“0”
“0”
“0”

Internal Communication Counter
(Every Internal Communication Cycle Adds +1)

 

CHANNEL STATUS

Channel Status shows the I/O module’s data error.  
  - Input overrange (≤ -15% or ≥ 115%) of Input modules except R6x-TSx and R6x-RSx. 
  - Inputs of R6x-TSx, R6x-RSx burnout.
  - Output wire breakdown of R6x-YSx (Firmware Version 2.00 or later). 
In the above case, the corresponded bit is “1.”

289

304

Module address 0
Module address 1
Module address 2

Module address 15

305

320

Unused

289

304

Module address 0
Module address 1
Module address 2

Module address 7

305

320

Module address 8
Module address 9
Module address 10

Module address 15

• Data Allocation Mode 1

• Data Allocation Mode 2

In the Data Allocation Mode 2, the LSB is used for channel 1, and the MSB for channel 2, of an analog module.

Summary of Contents for R6-NE1

Page 1: ...tem The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure the CE conform ity HOT INSERTION REMOVAL OF MODULES It is possible...

Page 2: ...to use the second channel of analog I O modules choose the Mode 2 The 2nd channel cannot be sent re ceived in the Mode 1 See COMPONENT IDENTIFICATION NETWORK SLOTS ON THE BASE Mount the Network Modul...

Page 3: ...smitting ON Blank OFF Note Be sure to set unused SW4 through 8 to OFF ETHERNET INDICATORS ID COLOR FUNCTION LINK Red ON at LINK DPLX Red ON with full duplex communication LINK10 Red ON with 10 Mbps co...

Page 4: ...info m system co jp EM 7787 Rev 7 P 4 9 TERMINAL CONNECTIONS Connect the unit as in the diagram below EXTERNAL DIMENSIONS unit mm inch 90 3 54 5 6 22 90 3 54 LOCKING CLAMP POSITIONING GUIDE 18 71 CON...

Page 5: ...er IP address in decimal ping with 32 bytes of data Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64...

Page 6: ...and a field of event bytes 13 Program Controller 14 Poll Controller 15 Force Multiple Coils X Digital output from the slave read write 16 Preset Multiple Registers X General purpose register within th...

Page 7: ...address 1 Ai 1 INT 3 Module address 2 Ai 1 INT 4 Module address 3 Ai 1 INT 16 Module address 15 Ai 1 INT 17 18 Module address 0 Ai 1 Float 19 20 Module address 1 Ai 1 Float 21 22 Module address 2 Ai...

Page 8: ...0 0 Internal Communication Counter Every Internal Communication Cycle Adds 1 CHANNEL STATUS Channel Status shows the I O module s data error Input overrange 15 or 115 of Input modules except R6x TSx a...

Page 9: ...verted into 0 to 10000 binary With C temperature unit raw data is multiplied by 10 For example 25 5 C is converted into 255 With F temperature unit the integer section of raw data is directly converte...

Reviews: