CONFORMITY WITH CE MARKING

 

CE MARKING

CE marking requires to integrate safety regulations existed in each country in EU territory and to secure smooth distribution 
of products of which safety is guaranteed.  It is mandatory by law that products distributed and sold in EU territory to have 
CE mark which shows that the product conforms with the requirements of EU Directive.  Each EU Directive describes the 
scope of apparatuses to which that EU Directive is applied.  M-System’s R7C must conform with EMC Directive.
Each Directive states only basic requirements.  In order to mark the CE on an assembled machinery equipment, its manufac-
turer needs to check the overall conformity with Directives applicable to it.

 

WARNINGS AND CAUTIONS WHEN INSTALLING THE R7C

The R7C needs to be installed in a control panel.  This is effective not only to ensure general safety but also to contain noise 
emissions by the R7C inside the control panel.  We conduct a series of testing to see that the product conforms to EMC Direc-
tive while it is installed in the control panel.
Warning and cautions when installing R7C are stated below.

• Use control panels with an internal panel plate, both made of metal, when installing the R7C.
• Make sure to adequately ground the control panel and the internal panel plate with a thick cable to maintain low imped-

ance at high frequency.

• Use shielded cables for the signals taken out of the control panel.
• Choose a thick and short cable to ground the FG terminal of the R7C module to the internal panel plate of the control panel.

    Note: If electromagnetic radiation disturbance increases by grounding the FG terminal, remove the grounding.

• When painting the internal plate of the control panel, apply masking to expose metal surface to secure conductivity at the 

sections where the following parts are attached:

  - Bolts attaching the internal panel to the control panel
  - Ground for the FG of the R7C module
  - Earth clamp on the shielded cable

• Noise emissions inside the control panel might leak through its openings.  Design them as small as possible.  Recommended 

diameter is 10 cm or less.

Supplement:

Additional measures may be taken depending upon actual installation sites.  These points of cautions are illustrated in the 
next page.

• Prevent noise leakage by wrapping cables using shield covers, shield tubes and flexible conduits etc. if noise leaks through 

the cable outlet.

• Use an electromagnetic shield gasket and block up the gap between the control panel cabinet and its cover, if noise leaks 

through it.

• Connecting the internal panel plate and the cover of the control panel to the main cabinet using an earth strap may be 

effective to strengthen the grounding.

• Electromagnetically shielded control panel cabinet is effective for shielding.

Summary of Contents for R7C-RS4

Page 1: ...orm ity Install lightning surge protectors for those wires connect ed to remote locations Choose a surge protector with its maximum surge voltage 40V or less between lines Rec ommended M System model...

Page 2: ...selected with the rotary switch 5 4 3 2 1 0 9 8 7 6 Baud Rate Setting 0 156 kbps 1 625 kbps 2 2 5 Mbps 3 5 Mbps 4 10 Mbps OPERATING MODE Factory setting Extension SW1 1 1 2 SW1 1 SW1 2 EXTENSION OFF...

Page 3: ...due to noise interference Missing parts of the data sent from the master ON OFF OFF OFF OFF Unable to receive data due to wire breakdown ON OFF ON OFF ON OFF Faulty Baud Rate and or Station Address se...

Page 4: ...5 5 22 DIN RAIL 35 mm wide 54 2 13 17 66 50 1 97 18 5 73 115 4 53 7 M3 SCREW TERMINALS for CC Link POWER 18 M3 SCREW TERMINALS for INPUT 6 24 6 24 CONNECTION DIAGRAM 4 7 6 3 2 5 1 0V 24V DC FG SLD DG...

Page 5: ...e Master Unit can be located other than at the extreme ends of communication line DATA ALLOCATION Analog input 0 Analog input 1 Analog input 2 Analog input 3 RWrn 0 1 2 3 Unused Unused Unused Unused R...

Page 6: ...t range error Input 2 Burnout input range error Unused Input 3 Burnout input range error Input 0 ADC error Input 1 ADC error Input 2 ADC error Input 3 ADC error Unused Burnout input range error 15 115...

Page 7: ...ng the R7C Make sure to adequately ground the control panel and the internal panel plate with a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out o...

Page 8: ...using an electro magnetically shielded control panel By connecting the internal panel plate and the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the con...

Page 9: ...Additional measures may be taken depending upon actual installation sites These points of cautions are illustrated in the next page Keep cables as short as possible It prevents noise emissions from th...

Page 10: ...m is not effective Points of cautions applicable when wiring the R7C Series To external apparatus Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of...

Reviews: