background image

R7F4DC-DA16A-H

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: info@m-system.co.jp

EM-7767-A  P. 2 / 7

COMPONENT IDENTIFICATION

Power

Error

RD

Run

SD

0

8

X

X

1

9

2

A

3

B

4

C

5

D

6

E

7

F

SW1

  

ON

TERM

ON

×10 SA ×1

Input Connector

Power Supply / Exc. Supply

Connector

CC-Link Connector

Terminator DIP SW

Status Indicator LED

Station Address
Setting Rotary SW

Discrete Input Status Indicator LED

Operation Mode Setting
DIP SW (SW1)

 

STATUS INDICATOR LED

ID

COLOR FUNCTION

Power

Green

ON when internal 5V power is in normal 
status.

Run

Green

ON when the communication is normal*

1

Error

Red

ON when the received data is abnormal.

SD

Green

ON when the module is transmitting.

RD

Green

ON when the module is receiving.

*1. Run LED turns off when no command is received from the 

master device.

 

DISCRETE INPUT STATUS INDICATOR LED

Green LED shows the input status.
  ON : LED ON
  OFF : LED OFF

 

STATION ADDRESS

The left switch determines the tenth place digit, while the 
right one does the ones place digit of the station address 
(1 - 64).
(Factory setting: 00)

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

0

9

8

7

6

Station Address Setting (x1)

Station Address Setting (x10)

 

OPERATING MODE

(*) Factory setting

• Baud Rate (SW1-1, 1-2, 1-3)

Baud Rate is selected with the DIP switch

BAUD RATE

SW1

1

2

3

156 kbps (*)

OFF

OFF

OFF

625 kbps

ON

OFF

OFF

2.5 Mbps

OFF

ON

OFF

5 Mbps

ON

ON

OFF

10 Mbps

OFF

OFF

ON

Note: Be sure to set unused SW1-4 to OFF.

 

TERMINATING RESISTOR

To use the terminating resistor, turn the switch ON, and 
OFF to invalidate. (Factory setting OFF)

Summary of Contents for R7F4DC-DA16A-H

Page 1: ...for the power source input and output connected to the unit etc POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 24V DC rating 24V 10 approx 26 mA GENERAL PRECAUTIONS Before you remove the unit or mount it turn off the power supply and input signal for safety Before you remove the connector or mount it mak...

Page 2: ...D Green ON when the module is transmitting RD Green ON when the module is receiving 1 Run LED turns off when no command is received from the master device DISCRETE INPUT STATUS INDICATOR LED Green LED shows the input status ON LED ON OFF LED OFF STATION ADDRESS The left switch determines the tenth place digit while the right one does the ones place digit of the station address 1 64 Factory setting...

Page 3: ...nt from the master ON OFF OFF OFF OFF Unable to receive data due to wire breakdown ON OFF ON OFF ON OFF Faulty Baud Rate and or Station Address setting OFF OFF OFF OFF OFF Power input removed or power supply failure OFF OFF ON ON BL Blinking 1 SD LED which is blinking may appear to be ON with high baud rate especially when fewer modules are connected 2 LED combinations indicated with do not occur ...

Page 4: ...d 3 GND 0V 3 GND 0V 4 X0 Input 0 4 X8 Input 8 X1 1 24V 24V DC X9 1 24V 24V DC 2 NC Unused 2 NC Unused 3 GND 0V 3 GND 0V 4 X1 Input 1 4 X9 Input 9 X2 1 24V 24V DC XA 1 24V 24V DC 2 NC Unused 2 NC Unused 3 GND 0V 3 GND 0V 4 X2 Input 2 4 XA Input 10 X3 1 24V 24V DC XB 1 24V 24V DC 2 NC Unused 2 NC Unused 3 GND 0V 3 GND 0V 4 X3 Input 3 4 XB Input 11 X4 1 24V 24V DC XC 1 24V 24V DC 2 NC Unused 2 NC Unu...

Page 5: ... from the DIN rail A C B DIN RAIL MOUNTING RIGHT ANGLE Mounting A Insert the longer DIN rail mounter slider until it clicks twice as shown below A B Set the upper hook at the rear side of the unit on the DIN rail C Push in the lower B C Note leave at least 10 mm 39 in at the both side of the unit Dismounting A Push down the DIN rail mounter slider with tip of a mi nus screwdriver B Pull the lower ...

Page 6: ...ide 4 16 2 4 3 17 dia 4 16 deep CONNECTION DIAGRAM Note In order to improve EMC performance bond the FE1 terminal to ground Caution FE1 terminal is NOT a protective conductor terminal DA DG DB SLD FE SNSR EXC SNSR EXC FE1 PWR PWR 1 2 4 5 3 SNSR EXC SNSR EXC FE1 PWR PWR 1 2 4 5 3 X0 GND NC GND NC 24V Input X0 1 2 4 3 Detection Circuit XF 24V 1 2 4 3 GND NC Xn 24V 1 2 4 3 Detection Circuit Input XF ...

Page 7: ...X n 0 0 Unused Unused Interval timed Response X Refresh Data Y I O DATA DESCRIPTIONS DISCRETE INPUT 0 15 Input 0 Input 1 Input 2 Input 3 Input 15 0 OFF 1 ON 0 OFF 1 ON 0 OFF 1 ON 0 OFF 1 ON 0 OFF 1 ON COMMUNICATION CABLE WIRING DA DB DG SLD FG DA DB DG SLD FE R7F4DC DA DB DG SLD FE R7F4DC 1 Master module Terminating Resistor blue white yellow 1 Turn on the terminator DIP switch to activate the int...

Reviews: