COMPONENT IDENTIFICATION

T1 T2 T3 T4

T5 T6 T7

1A 1B 1C 3A 3B 3C 5A 5B 5C 7A 7B 7C 9A 9B 9C 11A 11B

ALM

+

ALM

11C

2A 2B 2C 4A 4B 4C 6A 6B 6C 8A 8B 8C 10A 10B 10C 12A 12B 12C

TRG

+

TRG

RUN Indicator LED COMM Indicator LED

ERR Indicator LED

TRIG Indicator LED

ALM Indicator LED

RS-485 Connector

Configurator Jack

Node Address Setting

Rotary SW

Operating Mode

Setting Rotary SW

RS-232-C

9-pin Connector

Power / FG Terminals

 TOP VIEW

 REAR VIEW

Specifications

 

INDICATOR LED

RUN

Green LED blinks when the internal micro-
processor is operating normally.

COMM

:  

Communication LED.  Amber LED turns on 
when the RZMS is receiving normal data 
query frames from Modbus and sending re-
sponses out.

ERR

:  

Error LED.  Red LED turns on with internal 
errors and blinks when the RZMS is receiv-
ing abnormal data query frames from Mod-
bus.

 

ERR LED may also blink while the PC Re-
corder is not recording, however, it is not an 
abnormality or a failure of the RZMS as far 
as the LED turns off when the PC Recorder 
starts recording. (The RZMS blinks the ERR 
when it receives a break signal from certain 
types of PC designed to indicate an abnor-
mality when application programs are not in 
use of one or more COM ports.)

TRG

:  

Trigger LED.  Amber LED turns on when the 
trigger contact input turns on.

ALM

:  

Alarm LED.  Amber LED turns on when the 
alarm contact output turns on.

 

NODE ADDRESS SETTING ROTARY SW

1 through F

:   Setting at the power startup is recognized as 

the module’s node address.

0

:  

Setting with PC Configurator Software is 
enabled.  Software settings are deleted if the 
RZMS is started up with a setting other than 
zero (0). 

 

OPERATING MODE SETTING ROTARY SW

A/D conversion mode, service channel numbers, cold junction compensation, line noise filter frequency and burnout action for 
T/C and RTD input can be specified using this switch.
Setting with PC Configurator Software is enabled when the switch is set to zero (0), except that the cold junction compensa-
tion can be enabled/disabled for individual channels on the PC Recorder Software programs: MSR128LS and MSR128LV.  In 
order to protect the software setting before the power is turned off, be sure to turn the power supply on with ‘0’ setting.

1 through F

:   Combination of settings as shown in the table below.

0

:  

Last software setting before the power is turned off is enabled.

A/D

CONVERSION MODE

SERVICE

CHANNEL

NUMBERS

COLD JUNCTION

COMPENSATION

(T/C)

LINE NOISE FIL-

TER

FREQUENCY

BURNOUT (T/C and RTD)

All Channels

Individual
Channels

NONE

UP

DOWN

Medium

12

With

50/60 Hz

1

2

3

50 Hz

4

5

6

60 Hz

7

8

9

Without

50 Hz

A

B

C

60 Hz

D

E

F

Software setting for 

all channels (Fast, 

Medium, Slow)

Software setting 

(12 or 6)

Software setting 

for individual 

channels

Software setting 

for all channels 

(50, 60, 50/60 Hz)

0

Software

setting

Note 1: Specifying the exact frequency (50 Hz and 60 Hz) provides better protection than 50/60 Hz setting.
Note 2: Factory setting is ‘1.’

Summary of Contents for RZMS-U9

Page 1: ...e distances are maintained to con form to CE requirements Failure to observe these re quirements may invalidate the CE conformance The actual installation environments such as panel con figurations co...

Page 2: ...ve The potential of the open terminal C against the FG equals to that of the last scanned channel If ch 2 and ch 3 are not connected the accuracy of ch 4 measurement is affected by potential differenc...

Page 3: ...C port COM1 through COM5 supported LAN card LAN card by Windows 1 External e g SCSI devices may impair appropriate performance MSR128LS MSR128LV MSR128LS MSR128LV PC IBM PC AT or compatible Operating...

Page 4: ...on ALM Alarm LED Amber LED turns on when the alarm contact output turns on NODE ADDRESS SETTING ROTARY SW 1 through F Setting at the power startup is recognized as the module s node address 0 Setting...

Page 5: ...module from sliding down is recommended WALL MOUNTING Set the body so that its DIN rail adaptor is at the bottom Pull down the DIN rail adaptor Refer to EXTERNAL DIMENSIONS TERMINAL CONNECTIONS Connec...

Page 6: ...ion line via twisted pair cable when there is no cross wiring close across the terminal T2 T3 with the attached jumper pin or with a leadwire When the device is not at the end remove the jumper pin No...

Page 7: ...des the connections shown with solid lines in the figure below 2 Pins No 8 are not connected between each other May cause breakdowns Interlink or Reverse cables are usually applicable Pin Assignments...

Page 8: ...ifications therefore you usually do not need any cali bration However PC Configurator Software RZMSCFG is available to trim zero and span if such needs arise in order to adjust the input sensor range...

Reviews: