5.4 Surge Monitor Operation
This Mac Victor 2.0 standard feature monitors both the Input SPD Module and the Output Fuse (F1) on the
Output Surge & Filter Board Assembly.
Standard Surge Monitor Operation:
POWER ON (green LED) is ON during normal operation
SERVICE (red LED) is OFF during normal operation
SERVICE (red LED) is ON indicates Input SPD module must be replaced
(THOR#: TSi040R-150-1P10)
POWER ON (green LED) is OFF indicates loss of output power or the output Surge
& Filter Board Assembly Fuse (F1) must be replaced (THOR#: 0603-0004-01)