background image

Mac Victor 2.0 Installation Operation Manual 042408.pdf - © 2008 Mac Victor Power, LLC.

 

 

 Page 22 of 23 

 

7 – SPECIFICATIONS 

 

7.1  Mac Victor 2.0 Specifications  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 

7.2  UPS Specifications and Compatible UPS Models  

 
 

 

Capacity:

  2kVA (2000VA)  straight & locking blade / 3kVA (3000VA) locking blade only

 

 

Input:  

 

                 - 120Vac, 60hz, 1ph - 20A circuit breaker (2kVA)  
                 - 120Vac, 60hz, 1ph - 30A circuit breaker (3kVA)  
                 - Input SPD (Surge Protection Device) replaceable plug-in module type

 

 

Output:  

 

                 - 120Vac, 60hz, 1ph - 4 circuit breakers (20A) with Line and Neutral  

   conductors pre-wired to output terminal strips for hard wiring to remotely  
   located Isolated Ground (IG) receptacles for critical electronics 

                 - Isolated Ground bar and Chassis Ground bar for proper IG & ground wiring 
                 - Output line conditioner includes low impedance isolation transformer,  
                    electrical noise filtering, and output SPD (Surge Protection Device) 
                 - Optional 5

th

 circuit breaker (20A) for integrated IG receptacles (4 outlets)  

 

Operating Characteristics:

 

                 - Overall dimensions - 19”w x 15.75”h x 9.5”d (not including UPS)

 

                 - Weight: 85 lbs. (2kVA) / 105 lbs. (3kVA) 
                 - Temperature:  0 - 30º C (32-86º F) 
                 - Humidity:  0% - 90% RH (non – condensing)

 

 

Listings / Patents: 

                 - U.L. 1778 Listed 4

th

 Edition – UPS Maintenance Bypass / Line Conditioner    

  Accessory.  The Mac Victor 2.0 is considered a “separately derived source” for  
  the termination of Isolated Ground conductors per the National Electrical Code.

 

                 - U.S. Patent Pending 

 

Product Features:

 

  - Plug & receptacle connectivity to many Uninterruptible Power Supply (UPS) vendors 

                 - UPS battery bypass switch (normal/bypass) – “Make before Break” type 
                 - Provides clean, isolated power for all loads (even in the UPS bypass switch mode)    
                 - Front Monitor Display alarms for Input SPD module & Output SPD fuse 

 

                 - Input & Output pilot lights on front panel for power status diagnostics

 

                 - Input & Output power monitoring dry contacts (form C) for remote signaling

 

                 - Conduit knockouts (1/2” & 3/4" concentric) on sides, top, bottom, & back 
                 - Remote switch capability provides output power off for fire emergency compliance

 

 

Options:  

 

                   - 5

th

 output circuit breaker (20A) for integrated IG receptacles (4 outlets)  

 

                   - Remote emergency shutdown of 5

th

 circuit / integrated IG receptacles 

 

 

See the UPS Specifications and Installation/Operation Manual from the UPS manufacturer. 

List of Mac Victor 2.0 Compatible UPS Models:

 

Manufacturer   

 

 

2kVA Model # 

 

 

 

3kVA Model # 

General Electric 

 

 

GT2000T  * 

 

 

 

 

GT3000T 

Liebert / Emerson   

 

GXT2-2000RT120  * 

 

 

GXT2-3000RT120 

Eaton Powerware   

 

PW9120-2000  * 

 

 

 

PW9120-3000 

Oneac 

 

 

 

 

S2KOXAU  ** 

 

 

 

S3KOXAU 

Chloride   

 

 

 

A2KOXAU  ** 

 

 

 

A3KOXAU 

    

 

 

 

 

 

* = use with MVP-2KS  

 

All 3kVA UPS use with MVP-3KL 

 

 

 

 

 

 

** = use with MPV-2KL 

 

 

CAUTION: Important UPS limitations

 

UPS External Battery cabinets are not permitted on the Mac Victor 2.0 Shelf and must be located separately 

Maximum UPS width = 8.6 inches / Maximum UPS weight = 95 lbs. 

 

UPS installed on top of the 

mounting shelf 

See UPS Manual for exact 

dimensions 

Typical height is 14” – 17” 

Maximum width = 8.6”  

19” 

Figure 7.1  

9.5” 

15.75” 

Summary of Contents for MVP-2KL

Page 1: ...acles along with plug and receptacle connectivity for the Uninterruptible Power Supply UPS The mission of Mac Victor is to Expand Your Power by enhancing the return on investment of your Critical Elec...

Page 2: ...ts 4 2 Location 4 3 Typical Elevation 4 4 Mounting Instructions 4 5 Wiring Diagram Mac Victor 2 0 4 6 Wiring Diagram Remote Power Off 4 7 Wiring Diagram Remote signaling of Input and Output power stat...

Page 3: ...isconnect Switch may be required to de energize the equipment before servicing Service is to be performed by qualified personnel only See Installation Instructions before connecting to the supply The...

Page 4: ...he UPS outlets Do not plug other equipment into the other UPS outlets except for the Mac Victor 2 0 plug assembly Equipment plugged into the other UPS outlets will not function in the bypass mode and...

Page 5: ...acles by injecting electrical noise onto the IG conductor The National Electrical Code NEC allows for an alternative IG grounding method through the use of a separately derived system such as an isola...

Page 6: ...r off relay to the Isolation Transformer with neutral to ground bond Output Surge filter board assembly provides additional surge power protection and noise filtering Output Surge filter board assembl...

Page 7: ...S IG Base Item Number Description MVP 2KS 2kVA Mac Victor 2 0 w straight blade UPS connectors NEMA 5 20P 5 20R MVP 2KL 2kVA Mac Victor 2 0 w locking blade UPS connectors NEMA L5 20P L5 20R MVP 3KL 3kV...

Page 8: ...rical Code NEC NFPA 70 IG Suffix Isolated Ground receptacle option Integrated Isolated Ground Receptacles Option IG suffix includes 4 outlets and a 5th output circuit breaker The Integrated Isolated G...

Page 9: ...closet telecom equipment wall datacom room or other secure locations that are not accessible to the public To minimize the distance of branch circuit runs to the remote Isolated Ground receptacles ch...

Page 10: ...drivers etc Installation Steps Wood Stud Mounting 1 Locate 2 adjacent wooden studs 16 on center at the desired installation location 2 BE SURE TO ACCOUNT FOR THE HEIGHT OF THE UPS TO BE INSTALLED ON T...

Page 11: ...iring must be run in separate conduit from all output wiring All output wiring must be run in dedicated conduits or MC cable and not routed with any other equipment wiring to avoid induced voltages Re...

Page 12: ...ower status pilot lights or to provide dry contact status signals to the inputs of Building Automation Systems Input Power Terminals TS 1 Remote Power Off Relay R1 Remote Power Off Switch maintained N...

Page 13: ...on AHJ and only in gasoline fueling applications These special applications can have fueling data boxes plugged into the IG outlets that may need to be shut down during fueling emergencies This option...

Page 14: ...and latch the front hinged enclosure cover 5 Turn on the input power circuit breaker MB 1 located at the lower front right of the enclosure 6 The Input Power pilot should come on 7 Set the UPS Bypass...

Page 15: ...2 0 Shelf with the front of the UPS facing to the left outlets and power cord facing the right 4 The UPS should be located on the shelf in a position that insures adequate rear ventilation of the UPS...

Page 16: ...ecure any excess cabling 6 Insert the Safety Outlet Protector Plugs included on all open outlets on the back of the UPS 7 Follow the UPS power up procedures as outlined in the accompanying UPS Manual...

Page 17: ...F1 on the Output Surge Filter Board Assembly Standard Surge Monitor Operation POWER ON green LED is ON during normal operation SERVICE red LED is OFF during normal operation SERVICE red LED is ON ind...

Page 18: ...ing up UPS switch back to Normal When the Switch is in Bypass if there is a utility power outage the output power will go off LOSS OF INPUT POWER Input light is OFF and Output light is ON Indication o...

Page 19: ...nd then switch back to the On position If a circuit breaker continues to open check for a circuit overload or a wiring fault A qualified electrician may be required to safely diagnose this problem Sur...

Page 20: ...See Section 6 1 Input circuit breaker trips Overloaded system Remove excess load reset breaker See Section 6 3 UPS output circuit breaker trips Overloaded system Remove excess load reset breaker See...

Page 21: ...fast acting 1 10 amp THOR 0603 0100 02 Mac Victor 2 0 Output SPD Filter Board Assy Located at the bottom of the enclosure TB 1 Relay Output Power TB 2 Relay Input Power Fuse F 2 Fuse F 3 Fuse F 1 Outp...

Page 22: ...al Electrical Code U S Patent Pending Product Features Plug receptacle connectivity to many Uninterruptible Power Supply UPS vendors UPS battery bypass switch normal bypass Make before Break type Prov...

Page 23: ...LLC 10500 Wakeman Drive Suite 105 Fredericksburg VA 22407 Phone 540 220 8116 Fax 540 242 7004 www MacVictor com Mac Victor and Expand Your Power are registered U S trademarks of Mac Victor Power LLC M...

Reviews: