1 - IMPORTANT SAFETY INSTRUCTIONS 

 

1.1  Save these Instructions 

This manual contains important instructions and specifications for the Mac Victor 2.0 that should be 
followed during installation and maintenance. 

 

CAUTION:  Risk of Personal Injury and Equipment Damage.   
Before attempting to install and power up the Mac Victor 2.0, carefully read 
this manual.  Keep this manual with the Mac Victor 2.0 for future references.  
All service work must be done by qualified personnel.  Do not attempt to 
service the Mac Victor 2.0 unless you have had proper training. 
 
WARNING:  Risk of Electrical Shock and Personal Injury.  Opening or 
removing covers risk the exposure to dangerous voltages!

 

 
 

While every effort has been made to ensure the completeness and accuracy of this manual, 
Mac Victor Power, LLC and THOR SYSTEMS, Inc. accept no responsibility or liability for 
any loss or damage resulting from the use of the information contained in this document. 
This complete document shall not be copied or reproduced without the written permission 
of Mac Victor Power, LLC.  Due to technical improvements, some of the information 
contained in this manual may be changed without notice.

 

 

1.2  General 

 

WARNING:  RISK OF ELECTRICAL SHOCK AND PERSONAL INJURY. 

 

More than one Disconnect Switch may be required to de-energize the equipment before 
servicing.  Service is to be performed by qualified personnel only! 

 

See Installation Instructions before connecting to the supply. 

 

The Mac Victor 2.0 provides plug and receptacle interfacing with selected models of 
Uninterruptible Power Supplies (hereafter UPS) manufactured by others.  See the 
accompanying UPS Installation Instructions before connecting to the supply.  All UPS that are 
used must be “Mac Victor 2.0 Compatible UPS”. (See Section 7.2 for list of Compatible UPS)  

 

All UPS units have internal batteries as part of the product package.  Dangerous voltages may 
still be present even when all external voltage sources have been de-energized. 

 

The UPS should be bypassed, turned off and disconnected during maintenance or service work. 

 

1.3  Installation 

 

The Mac Victor 2.0 base unit should be installed by a licensed electrical contractor. 

 

The UPS can be installed and started up by qualified office technical personnel. 

 

To reduce the risk of electric shock, install the Mac Victor 2.0 and the UPS in a temperature 
and humidity controlled indoor area free of conductive contaminants. 

 

Ambient temperature must not exceed 30ºC (86ºF).  Optimal battery life of peripheral UPS is 
also obtained if the ambient temperature does not exceed 30ºC (86ºF). 

 

It is important that both the Mac Victor 2.0 and the UPS have adequate ventilation.  Maintain 
air movement around and through the units.  Do not block the air vents. 

 

Avoid installing the units in direct sunlight or near heat sources. 

Summary of Contents for MVP-2KL

Page 1: ...acles along with plug and receptacle connectivity for the Uninterruptible Power Supply UPS The mission of Mac Victor is to Expand Your Power by enhancing the return on investment of your Critical Elec...

Page 2: ...ts 4 2 Location 4 3 Typical Elevation 4 4 Mounting Instructions 4 5 Wiring Diagram Mac Victor 2 0 4 6 Wiring Diagram Remote Power Off 4 7 Wiring Diagram Remote signaling of Input and Output power stat...

Page 3: ...isconnect Switch may be required to de energize the equipment before servicing Service is to be performed by qualified personnel only See Installation Instructions before connecting to the supply The...

Page 4: ...he UPS outlets Do not plug other equipment into the other UPS outlets except for the Mac Victor 2 0 plug assembly Equipment plugged into the other UPS outlets will not function in the bypass mode and...

Page 5: ...acles by injecting electrical noise onto the IG conductor The National Electrical Code NEC allows for an alternative IG grounding method through the use of a separately derived system such as an isola...

Page 6: ...r off relay to the Isolation Transformer with neutral to ground bond Output Surge filter board assembly provides additional surge power protection and noise filtering Output Surge filter board assembl...

Page 7: ...S IG Base Item Number Description MVP 2KS 2kVA Mac Victor 2 0 w straight blade UPS connectors NEMA 5 20P 5 20R MVP 2KL 2kVA Mac Victor 2 0 w locking blade UPS connectors NEMA L5 20P L5 20R MVP 3KL 3kV...

Page 8: ...rical Code NEC NFPA 70 IG Suffix Isolated Ground receptacle option Integrated Isolated Ground Receptacles Option IG suffix includes 4 outlets and a 5th output circuit breaker The Integrated Isolated G...

Page 9: ...closet telecom equipment wall datacom room or other secure locations that are not accessible to the public To minimize the distance of branch circuit runs to the remote Isolated Ground receptacles ch...

Page 10: ...drivers etc Installation Steps Wood Stud Mounting 1 Locate 2 adjacent wooden studs 16 on center at the desired installation location 2 BE SURE TO ACCOUNT FOR THE HEIGHT OF THE UPS TO BE INSTALLED ON T...

Page 11: ...iring must be run in separate conduit from all output wiring All output wiring must be run in dedicated conduits or MC cable and not routed with any other equipment wiring to avoid induced voltages Re...

Page 12: ...ower status pilot lights or to provide dry contact status signals to the inputs of Building Automation Systems Input Power Terminals TS 1 Remote Power Off Relay R1 Remote Power Off Switch maintained N...

Page 13: ...on AHJ and only in gasoline fueling applications These special applications can have fueling data boxes plugged into the IG outlets that may need to be shut down during fueling emergencies This option...

Page 14: ...and latch the front hinged enclosure cover 5 Turn on the input power circuit breaker MB 1 located at the lower front right of the enclosure 6 The Input Power pilot should come on 7 Set the UPS Bypass...

Page 15: ...2 0 Shelf with the front of the UPS facing to the left outlets and power cord facing the right 4 The UPS should be located on the shelf in a position that insures adequate rear ventilation of the UPS...

Page 16: ...ecure any excess cabling 6 Insert the Safety Outlet Protector Plugs included on all open outlets on the back of the UPS 7 Follow the UPS power up procedures as outlined in the accompanying UPS Manual...

Page 17: ...F1 on the Output Surge Filter Board Assembly Standard Surge Monitor Operation POWER ON green LED is ON during normal operation SERVICE red LED is OFF during normal operation SERVICE red LED is ON ind...

Page 18: ...ing up UPS switch back to Normal When the Switch is in Bypass if there is a utility power outage the output power will go off LOSS OF INPUT POWER Input light is OFF and Output light is ON Indication o...

Page 19: ...nd then switch back to the On position If a circuit breaker continues to open check for a circuit overload or a wiring fault A qualified electrician may be required to safely diagnose this problem Sur...

Page 20: ...See Section 6 1 Input circuit breaker trips Overloaded system Remove excess load reset breaker See Section 6 3 UPS output circuit breaker trips Overloaded system Remove excess load reset breaker See...

Page 21: ...fast acting 1 10 amp THOR 0603 0100 02 Mac Victor 2 0 Output SPD Filter Board Assy Located at the bottom of the enclosure TB 1 Relay Output Power TB 2 Relay Input Power Fuse F 2 Fuse F 3 Fuse F 1 Outp...

Page 22: ...al Electrical Code U S Patent Pending Product Features Plug receptacle connectivity to many Uninterruptible Power Supply UPS vendors UPS battery bypass switch normal bypass Make before Break type Prov...

Page 23: ...LLC 10500 Wakeman Drive Suite 105 Fredericksburg VA 22407 Phone 540 220 8116 Fax 540 242 7004 www MacVictor com Mac Victor and Expand Your Power are registered U S trademarks of Mac Victor Power LLC M...

Reviews: