background image

Mac Victor 2.0 Installation Operation Manual 042408.pdf - © 2008 Mac Victor Power, LLC.

 

 

 Page 20 of 23 

 

6.4  UPS (Uninterruptible Power Supply)   

See the UPS Installation / Operation Manual from the UPS manufacturer. 
 
 

6.5  Troubleshooting Chart   

 

Problem                Possible Cause                Solution   

 
Connected loads not operating  

Output circuit breakers turned off   

Turn on the output breakers 

during normal operation   

 

(See Section 6.3) 

 
Connected loads not operating  

UPS turned off 

 

 

 

 

 

 

Verify UPS is turned on  

during loss of power   

 

 

Bypass switch in “bypass” mode 

 

 

Move Bypass switch to “normal” mode 

 

 

 

 

 

 

 

 

 

(See Section 6.1) 

 
Input circuit breaker trips  

 

Overloaded system  

 

 

 

 

 

Remove excess load / reset breaker 

 

 

 

 

 

 

 

 

 

(See Section 6.3) 

 
UPS output circuit breaker trips  Overloaded system  

 

 

 

 

 

Remove excess load / reset breaker 

(See UPS operation manual) 

 
Output circuit breaker trips   

Overloaded circuit  

 

 

 

 

 

Remove excess load / reset breaker 

(See Section 6.3) 

 
Front display is in alarm   

 

Input SPD Module is bad   

 

 

 

Replace Input SPD module 

(See Section 5.4)   

 

 

 

 

 

(See Section 6.6) 

 
Front display is off 

 

 

 

Output SPD Fuse-F1 is bad  

 

 

Replace output SPD Fuse F-1 

(See Section 5.4)   

 

 

 

 

 

(See Section 6.6) 

 
Input status Relay (TB-2)   

 

Fuse F-3 is bad  

 

 

 

 

 

 

Replace Fuse F-3 

is not operating 

 

 

 

 

(See Section 6.6)   

 

 

 

 

 

(See Section 6.6) 

 
Output status Relay (TB-1)  

 

Fuse F-2 is bad  

 

 

 

 

 

 

Replace Fuse F-2 

is not operating 

 

 

 

 

(See Section 6.6)   

 

 

 

 

 

(See Section 6.6) 

 
 
 
 
 
 

Summary of Contents for MVP-2KS

Page 1: ...tacles along with plug and receptacle connectivity for the Uninterruptible Power Supply UPS The mission of Mac Victor is to Expand Your Power by enhancing the return on investment of your Critical Electronic Systems Mac Victor and Expand Your Power are registered U S trademarks of Mac Victor Power LLC The Mac Victor 2 0 is an ultra high quality power system that provides a centralized and wall mou...

Page 2: ...nts 4 2 Location 4 3 Typical Elevation 4 4 Mounting Instructions 4 5 Wiring Diagram Mac Victor 2 0 4 6 Wiring Diagram Remote Power Off 4 7 Wiring Diagram Remote signaling of Input and Output power status 4 8 Wiring Diagram Optional 5th Circuit IG Outlet and Optional Remote Off 5 STARTUP OPERATION 14 5 1 Power up of the Mac Victor 2 0 5 2 Installation and Strapping of the UPS 5 3 Power up of the UP...

Page 3: ...Disconnect Switch may be required to de energize the equipment before servicing Service is to be performed by qualified personnel only See Installation Instructions before connecting to the supply The Mac Victor 2 0 provides plug and receptacle interfacing with selected models of Uninterruptible Power Supplies hereafter UPS manufactured by others See the accompanying UPS Installation Instructions ...

Page 4: ...the UPS outlets Do not plug other equipment into the other UPS outlets except for the Mac Victor 2 0 plug assembly Equipment plugged into the other UPS outlets will not function in the bypass mode and will not receive maximum power protection from the system Avoid spilling liquids on or dropping any foreign object onto the Mac Victor 2 0 or the UPS Do not plug a laser printer or other household ap...

Page 5: ...tacles by injecting electrical noise onto the IG conductor The National Electrical Code NEC allows for an alternative IG grounding method through the use of a separately derived system such as an isolation transformer that allows for the re establishment of the Neutral to Ground bond on the output wiring This Neutral to Ground bond also known as a newly derived Neutral provides an acceptable locat...

Page 6: ...er off relay to the Isolation Transformer with neutral to ground bond Output Surge filter board assembly provides additional surge power protection and noise filtering Output Surge filter board assembly provides signal relays for Input and Output Power remote status Output Surge filter board assembly provides supply power fuse status signal to panel monitor Output power status pilot light is illum...

Page 7: ...KS IG Base Item Number Description MVP 2KS 2kVA Mac Victor 2 0 w straight blade UPS connectors NEMA 5 20P 5 20R MVP 2KL 2kVA Mac Victor 2 0 w locking blade UPS connectors NEMA L5 20P L5 20R MVP 3KL 3kVA Mac Victor 2 0 w locking blade UPS connectors NEMA L5 30P L5 30R Option Item Suffix Description Add suffix IG Optional 5th output circuit breaker and integrated Isolated Ground receptacles 4 outlet...

Page 8: ...trical Code NEC NFPA 70 IG Suffix Isolated Ground receptacle option Integrated Isolated Ground Receptacles Option IG suffix includes 4 outlets and a 5th output circuit breaker The Integrated Isolated Ground Receptacle Option and breaker are located on the left hand side of the cabinet NOTE When using this option it may be necessary to remove the left hand side panel 5 screws to improve access to t...

Page 9: ...r closet telecom equipment wall datacom room or other secure locations that are not accessible to the public To minimize the distance of branch circuit runs to the remote Isolated Ground receptacles choose a relatively central location if possible to mount the Mac Victor 2 0 A location relatively close to a circuit breaker panel is also preferred since a single 120Vac single phase circuit Line Neu...

Page 10: ...wdrivers etc Installation Steps Wood Stud Mounting 1 Locate 2 adjacent wooden studs 16 on center at the desired installation location 2 BE SURE TO ACCOUNT FOR THE HEIGHT OF THE UPS TO BE INSTALLED ON TOP OF THE MAC VICTOR 2 0 SHELF WHEN DETERMINING THE MOUNTING LOCATION 3 Determine the desired mounting height and mark on the wall centered on one of the wood studs the desired location of the top of...

Page 11: ...wiring must be run in separate conduit from all output wiring All output wiring must be run in dedicated conduits or MC cable and not routed with any other equipment wiring to avoid induced voltages Replace the Input SPD module if the front panel surge monitor goes into alarm condition See Section 4 6 for the wiring diagram for the Remote Power Off function See Section 4 7 for the wiring diagram f...

Page 12: ...power status pilot lights or to provide dry contact status signals to the inputs of Building Automation Systems Input Power Terminals TS 1 Remote Power Off Relay R1 Remote Power Off Switch maintained N C contacts Toggle Switch or Push Pull Switch Open for shutdown Close to restore power Remove Jumper and install Remote Power Off Switch N C contacts Power Status Terminal Blocks 11 16 on TS 1 Input ...

Page 13: ...ion AHJ and only in gasoline fueling applications These special applications can have fueling data boxes plugged into the IG outlets that may need to be shut down during fueling emergencies This option disconnects both Line and Neutral wiring Remote Power Source for emergency shutdown of gasoline fueling system Loss of 120Vac power opens relay R2 and turns off Circuit 5 IG outlets Restoration of 1...

Page 14: ... and latch the front hinged enclosure cover 5 Turn on the input power circuit breaker MB 1 located at the lower front right of the enclosure 6 The Input Power pilot should come on 7 Set the UPS Bypass Switch to the Bypass position 8 The Output Power pilot should come on The SPD Monitor should also come on 9 Turn on the output circuit breakers 1 4 If the integrated IG receptacle option is used turn...

Page 15: ... 2 0 Shelf with the front of the UPS facing to the left outlets and power cord facing the right 4 The UPS should be located on the shelf in a position that insures adequate rear ventilation of the UPS surface facing the back wall according to the UPS Manual Do not block the UPS ventilation holes 5 The Mac Victor 2 0 comes with 2 8 straps wide polypropylene 600 lb rated 2 wire buckles and 4 edge pr...

Page 16: ...secure any excess cabling 6 Insert the Safety Outlet Protector Plugs included on all open outlets on the back of the UPS 7 Follow the UPS power up procedures as outlined in the accompanying UPS Manual 8 Wait until the UPS has gone through all diagnostic self checks and is fully operational 9 Set the Mac Victor 2 0 Bypass Switch to the Normal Position Uninterruptible Power Supply UPS Figure 5 2 Mac...

Page 17: ...e F1 on the Output Surge Filter Board Assembly Standard Surge Monitor Operation POWER ON green LED is ON during normal operation SERVICE red LED is OFF during normal operation SERVICE red LED is ON indicates Input SPD module must be replaced THOR TSi040R 150 1P10 POWER ON green LED is OFF indicates loss of output power or the output Surge Filter Board Assembly Fuse F1 must be replaced THOR 0603 00...

Page 18: ...ting up UPS switch back to Normal When the Switch is in Bypass if there is a utility power outage the output power will go off LOSS OF INPUT POWER Input light is OFF and Output light is ON Indication of a utility power outage OR Indication of input circuit breaker tripped or turned off If there is not a power outage check the circuit breaker UPS is keeping the output power energized Do NOT switch ...

Page 19: ...and then switch back to the On position If a circuit breaker continues to open check for a circuit overload or a wiring fault A qualified electrician may be required to safely diagnose this problem Surge Monitor Operation Standard Monitor and Alarm See Section 5 4 for complete operation and troubleshooting Figure 6 4 Figure 6 5 Optional 5th Circuit Breaker and integrated Isolated Ground IG Recepta...

Page 20: ...e See Section 6 1 Input circuit breaker trips Overloaded system Remove excess load reset breaker See Section 6 3 UPS output circuit breaker trips Overloaded system Remove excess load reset breaker See UPS operation manual Output circuit breaker trips Overloaded circuit Remove excess load reset breaker See Section 6 3 Front display is in alarm Input SPD Module is bad Replace Input SPD module See Se...

Page 21: ... fast acting 1 10 amp THOR 0603 0100 02 Mac Victor 2 0 Output SPD Filter Board Assy Located at the bottom of the enclosure TB 1 Relay Output Power TB 2 Relay Input Power Fuse F 2 Fuse F 3 Fuse F 1 Output SPD fuse Replacement Fuse F 1 Class CC time delay 8 amp THOR 0603 0004 01 Figure 6 7 Replacement Input SPD module THOR TSi040R 150 1P10 Includes mounting base and replacement module ...

Page 22: ...onal Electrical Code U S Patent Pending Product Features Plug receptacle connectivity to many Uninterruptible Power Supply UPS vendors UPS battery bypass switch normal bypass Make before Break type Provides clean isolated power for all loads even in the UPS bypass switch mode Front Monitor Display alarms for Input SPD module Output SPD fuse Input Output pilot lights on front panel for power status...

Page 23: ... LLC 10500 Wakeman Drive Suite 105 Fredericksburg VA 22407 Phone 540 220 8116 Fax 540 242 7004 www MacVictor com Mac Victor and Expand Your Power are registered U S trademarks of Mac Victor Power LLC Manufactured by THOR SYSTEMS INC www ThorSystems US 804 355 1100 804 355 8900 fax 3621 Saunders Avenue Richmond VA 23227 4354 ...

Reviews: