Multi-Function Water To Water Heat Pump
7.4 Wiring construction must be installed by professional technicians refer to circuit diagram.
7.5 Power lines and signal line layout should be neat, rational, strong and weak lines separate and can
not interfere with each other, while not contacted with the connecting pipe and the valve body.
7.6 When power lines and control lines parallel, the wires were placed in each tube, also leave appropriate
distance between the lines.
7.7 Unit electric wire connection: take the unit power line, remote control three core lines, electric heater
power line, solar circulated water pump control power line, water tank temperature sensing line, solar
collector temperature sensor line, terminal equipments connect to unit lines, through the unit wiring
hole set into the electrical box, connect to the appropriate terminals according to wiring diagram, and
fix it by the pressure line of board in the electrical box.
7.8.Unit control panel Code MK3051, Fuse specifications: 5A/250V
8. Electrical Wire Selection
8
.1 Voltage drop occur may due to the large current draw during compressor starting, and may be result
in the compressor is difficult to stat. So we recommend selecting the wire specification from the table
below.
8.2.Size Table of Electrical Wire
within 5m
2.0
3.5
5.5
8.0
Within 10m
2.0
3.5
5.5
8.0
14.0
Within 15m
2.0
3.5
5.5
8.0
14.0
22.0
Within 20m
3.5
5.5
8.0
14.0
22.0
30.0
Within 30m
5.5
8.0
14.0
22.0
30.0
38.0
50.0
Within 50m
8.0
14.0
22.0
30.0
38.0
50.0
60.0
80.0
Within 1m
2.0
3.5
5.5
8.0
14.0
Starting current
(A)
Below 20
Below 30
Below 40
Below 50
Below 60
Below 70
Below 80
Below 90
Below 100
Below 110
Below 120
Below 140
Below 160
Below 180
Below 200
Below 220
Below 240
Markor Mark
(Heat resistance temperature above 60
)
The wiring specifications (mm2)
Mark
(Heat resistance
temperature above 120
)
Power supply
PCB
Unit
1
2
Compressor
COM
Power supply installation condition: The touching space of breaker should be more than 3mm,
use copper wire only.