© 2018 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com 53
Rev. Date 040218
The fuse disconnect switch is an optional
component offered by MacroAir. Reference page 5
for fuse size based upon the incoming power and
fan diameter.
4.1.1:
Mount the fuse disconnect switch outside of
the swept area of the fan airfoils.
4.1.2:
Wire the power cable from the fan to the
bottom of the fuse block. Then wire the incoming
power source to the disconnect switch.
4.1.3:
In the diagram below, a three phase system
is shown. For a single phase system, phase 1
would be connected to L1, neutral would be
connected to L2, and L3 would be left not
terminated.
4.1 Fuse Disconnect Switch
Installation
(Recommended but Optional)
C
Components:
A
- Fuse Block (Optional Add-On)
B
- Disconnect Switch (Optional Add-On)
C
- Class gG Fast Acting Fuses (Not Provided) - refer to the fuse chart on page 5
NOTE: Ensure that there is no power when installing this component.
Means for disconnection with contact separation at least 3mm.
A
B
Service Disconnect (Required
per
NEC
,
OSHA
,
IEC
,
CE
and
UL
compliance).
Not Included -
Optional Add-On