Introduction
AVD 370/2 FAN
© 2019 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com
AVD 370/2 INSTALLATION MANUAL 90-30071-00 Rev A-01 Date: 030121
6
Clearance Guidelines
⚠
ATTENTION:
Sprinkler Systems and Fan Placement.
In any installation where fire sprinklers
are in place, do not interfere with their correct operation. Fans should be located no less than 3
feet below a sprinkler and placed central to each sprinkler quadrant.
⚠
ATTENTION:
Sprinkler Systems and Code Compliance.
Prior to installing fans, review all
codes applicable to sprinkler systems and fans to ensure code compliance. Refer to the wiring
diagrams packaged inside the control panel for proper installation. If further advice is needed,
you may contact our support staff. However, it is your sole responsibility to see that the
installation is completed to code and is correct.
General Information on Fan Placement and Spacing
⚠
ATTENTION:
Strobe and Performance.
If possible, avoid mounting fans directly below lights
or skylights to avoid any strobe effect caused by moving blades.
⚠
WARNING:
Mezzanine Placement.
If the building has a mezzanine, fans should be mounted
so a person cannot reach a fan in any way from the upper level/deck. Make certain that fans are
positioned so that blade tips are at least 3 feet away from any area where a person may be able
to extend outward to reach them.
Figure 1: Fan Clearance and Placement
⚠
ATTENTION:
The minimum distance of a fan to a wall or similar obstruction should be no
less than 1.5 times the diameter of the fan. Reference Figure 1.