7
2.4
Features
ETL LISTED to UL 61010-1, Certified to CAN/CSA Std. C22.2 No 61010-1
Low level meter capable of displaying from 0-5000 ppm of CO
2
Sensor Resolution of 50 PPM
The CD-6H uses an automated background calibration program to set the clean air level on a regular basis *
The CD-6MC uses a manual Calibration to set clean and polluted air levels using a Calibration Kit **
Selectable fan and alarm relay activation
5 A SPDT fan relay controls starters of ventilations
0.5 A N.O. or N.C. alarm relay connects to warning devices or control panels
4-20 mA Current Loop
Mounts on a standard 4x4 electrical box and becomes cover for the box
Supervised system: any internal detector problem will cause the fan & alarm relay to activate
Carbon Dioxide sensor has an expected 15-year life. EOL indicator after 180 months of sensor power-up
Calibration verification test kit is available. One screw allows access for gas test
*CD-6H Only
**CD-6MC Only
2.5
Specifications
Power: 3 W (max) from 12 to 24 VAC or 12 to 32 VDC
Current (max) @ 24 VDC: 126 mA in alarm (two relays), 108 mA (fan relay only) and 85 mA (standby)
Shipping Weight: 1 pound (0.45 kg)
Size: 4 1/2 x 4 x 2 1/8 in. (11.4 X 11.4 X 5.3 cm)
Color: White or dark gray
Connections: plugs/terminals
Mounting box: (not included) 4x4 electric
Fan relay: 5 A, 240 VAC, pilot duty, SPDT, latching or non-latching
Fan relay actuation: selectable at dIS (disabled), 600, 700, 800, 900…,
2000
(default)…, 4800, 4900, 5000 ppm
Fan Delay Settings of 0, 1,
3
(default), 5 and 10 minutes
Fan Relay Minimum Runtime settings are
0
(default), 3, 5, 10 or 15 minutes
Fan relay latching or
non-latching
(default) selectable
Alarm relay: 0.5A 120 V, 60 VA
Alarm relay actuation: selectable
N.O.
(default) or N.C.
Alarm relay settings: “dIS” (disabled), 900, 1000, 1100, 1200, …
4000
(default), ….4900, 5000
Current Loop, 4-20 mA for 0-5000 ppm CO
2
, selectable to off or
on
(default)
Buzzer: 85 dBA at 10cm settable to off or on (default)
Digital display: 4-digit LED selectable to off or
on
(default).
Operating Environment: 32°F to 122° F (0°C to 50°C), 10 to 90% RH non-condensing