Features
ETL LISTED Certified to CAN/CSA Std. C22.2 No 61010-1 Conforms to UL Std. 61010-1
Low level meter capable of displaying from 0-200 ppm of CO
The CM-6 meets the Uniform Building Code for enclosed garages and meets OSHA standards for CO exposure
Selectable fan and alarm relay activation
5 A SPDT fan relay controls starters of exhaust fans
0.5 A N.O. or N.C. alarm relay connects to warning devices or control panels
4-20 mA Current Loop
CM-6 mounts on a standard 4x4 electrical box and becomes cover for the box
Supervised system: any internal detector problem will cause the fan & Alarm relay to activate
Calibration kit is available. One screw allows access for calibration or gas test
Specifications
Power: 3 W (max) from 12 to 24 VAC or 12 to 32 VDC
Current @ 24 VDC: 75 mA in alarm (two relays), 50 mA (fan relay only) and 23 mA stand by
Shipping Weight: 1 pound (0.45 kg)
Size: 4 1/2 x 4 x 2 1/8 in. (11.4 X 11.4 X 5.3 cm)
Color: Dark gray
Connections: plugs/terminals
Mounting box: (not included) 4x4 electric
Fan relay: 5 A, 240 VAC, pilot duty, SPDT, latching or non-latching
Fan relay actuation: selectable at diS (disable), 15 ppm, 25 ppm, 35 ppm (default), 50 ppm or 100 ppm CO
Fan Delay Settings of 0, 1, 3 (default), 5 and 10 minutes
Fan Relay Minimum Runtime settings are 0 (default), 3, 5, 10 or 15 minutes
Fan relay latching or not latching (default) selectable
Alarm relay: 0.5A 120 V, 60 VA
Alarm relay actuation: selectable N.O. default or N.C.
Alarm relay settings: diS, 50 ppm, 100 ppm, 150 ppm and 200 ppm (default)
Current Loop, 4-20 mA for 0-200 ppm CO
,
selectable to off or on (default)
Buzzer: 85 dBA at 10cm settable to off (default) or on
Digital display: 3 digit LED selectable to off (default) or on.
Operating Environment: 0°F to 125° F (-18
C to 52
C).10 to 90% RH non-condensing