DMK-1 Installation Guide 

REV 

 1.0 

[34-2900-0065-9 ] 

|

 

P a g e

 

2

 

Application 

The Macurco DMK-1 is an air tight enclosure that provides a means to mount any Macurco gas detector to an air 
duct. By duct mounting a Macurco gas detector it can monitor the air inside of the duct and provide early detection 
of carbon monoxide or other gases moving through the HVAC system. The DMK-1 used with Macurco gas detectors 
can provide automatic control to prevent recirculation of these gases into additional areas by the air handling 
systems, fans and blowers in commercial and residential applications. 

2.1

 

Features 

 

Provides detection and monitoring of gas concentrations in ventilation ducts 

 

Clear cover allows view of detector, displays and status lights 

 

PC 

 Polycarbonate housing 

 

Injection Molding Grade, Flame Retardant, UV Stabilized 
 

Included with the DMK-1 

 

Enclosure with cover, gasket and screws 

 

Standoffs - hex aluminum 

 

Machine screws - Phillips head 

 

Strain relief/seal for wiring exit hole 

 

Nut for strain relief 

 

Sheet metal mounting screws 

 

Foam compression seals 

 

A full-size drill hole position template 
 

Not included with the DMK-1 

 

Macurco Gas Detector 

 

Input sampling tube: available in various lengths from HVAC and Security distributors 

 

Single gang type detectors, CM-E1 and GD-

2B, will need a 4” single gang mud

-ring 

2.2

 

Specifications 

 

Size: 6 1/4 x 6 1/4 x 3 1/2 inches (15.9 x 15.9 x 8.9 cm) 

 

Exhaust Tube: EMT, 1/2” (1.3 cm) diameter 6 1/2” length (16.5 cm)

 

 

Setscrew Adapters: EMT, 1/2” (1.3 cm)

 

 

Shipping Weight: 1.5 pounds (0.68 kg) 

 

 

Summary of Contents for DMK-1

Page 1: ...IMPORTANT Keep these user instructions for reference Macurco DMK 1 Duct Mount Kit Installation Guide ...

Page 2: ...nings 3 2 Application 4 2 1 Features 4 2 2 Specifications 4 3 Installation Instructions 5 3 1 Location 5 3 2 Assembly Instructions 5 3 3 Installation 7 3 4 Pressure Differential Testing 8 3 5 Mounting the Detector 9 4 Maintenance 10 5 Appendix 11 6 Macurco Gas Detection Product limited warranty 12 ...

Page 3: ...at 1 844 325 3050 This detector helps monitor for the presence and concentration level of a certain specified airborne gas Misuse may produce an inaccurate reading which means that higher levels of the gas being monitored may be present and could result in overexposure and cause serious injury or death For proper use see supervisor or User manual or contact Technical Support at 1 844 325 3050 The ...

Page 4: ...tions in ventilation ducts Clear cover allows view of detector displays and status lights PC Polycarbonate housing Injection Molding Grade Flame Retardant UV Stabilized Included with the DMK 1 Enclosure with cover gasket and screws Standoffs hex aluminum Machine screws Phillips head Strain relief seal for wiring exit hole Nut for strain relief Sheet metal mounting screws Foam compression seals A f...

Page 5: ... at return air opening within the compartment where the air exits each compartment or in the duct system before air enters the return air system common to more than one compartment 3 2 Assembly Instructions 3 2 1 Remove the clear cover from the enclosure and remove the contents 3 2 2 Insert conduit setscrew adapters into the two large holes in the back of the enclosure Install the nuts for setscre...

Page 6: ...utside of the enclosure as pictured 3 2 6 Install the exhaust tube into the downstream setscrew adapter with the open end of the 45 degree cut facing downstream 3 2 7 Install the appropriately sized sampling tube not provided into the upstream setscrew adapter with the ports facing upstream Important The sampling tube MUST extend at least 2 3 into the width of the duct ...

Page 7: ... the six 6 holes to be drilled 3 3 2 Drill two 2 large and four 4 small holes in the duct you want to mount the unit on using the template provided The two large holes 1 are for the sampling and exhaust tubes The four small holes 1 16 are starter holes for the sheet metal mounting screws Ensure that the intake and exhaust tube holes are large enough to allow all the setscrew adapters to fit 3 3 3 ...

Page 8: ...n and use the manometer to measure the differential pressure between the two sampling tubes The differential pressure should measure at least 0 01 inches of water and no more than 1 11 inches of water Check the following if the differential pressure measurements are outside of the specified range Ensure that the air velocity in the duct is within the specified range If necessary use a velocity met...

Page 9: ...ctions provided for the detector 3 5 3 Install the gas detector onto the top of the four 4 standoffs Secure it in place using the four 4 remaining machine screws Important Be sure that there is a good seal between the DMK 1 and the duct surface around the sampling and exhaust tubes to ensure appropriate air flow through the DMK 1 and to the detector 3 5 4 Test the installed detector as described i...

Page 10: ...n under the cover and to clean the vented sampling inlets WARNING Do not blow out the sensor with compressed air Using compressed air may damage the sensor causing the sensor to not respond to the target gas WARNING High voltage terminals 120 240 VAC are located within the Macurco 12 series detectors presenting a hazard to service technicians Only qualified technicians should open the detector cas...

Page 11: ...DMK 1 Installation Guide REV 1 0 34 2900 0065 9 11 P a g e 5 Appendix DMK 1 Drill Hole Position Template External Dimensions 6 299 x 6 299 x 3 543 in ...

Page 12: ...CHANTABILITY AND FITNESS FOR PARTICULAR PURPOSE ARE LIMITED TO A PERIOD OF TWO 2 YEARS FROM THE PURCHASE DATE Macurco shall not be liable for any incidental or consequential damages for breach of this or any other warranty express or implied arising out of or related to the use of said gas detector The manufacturer or its agent s liability shall be limited to replacement or repair as set forth abo...

Reviews: