INSTALLATION INSTRUCTIONS

 

 

Models:

 

 

 

 

 
 

 

Use this product according to this instruction manual. 

 

Please keep this instruction manual for future reference.

 

 
 
 
 

General

 

The LED Horn Strobe is designed for easy installation.

 

 The model is for 24VDC operation.

 

 
 

WARNING:

 

Please read these instructions carefully before using this product.

 

 Failure to comply with any of 

the  following  instruction,  cautions  and  warnings  could  result  in  Improper  application,  candela  setting, 
installation and/or operation of this product in an emergency situation, which could result in property 
damage and serious injury or death to you and/or others.

 

SPECIFICATIONS

 

 

 

CURRENT DRAW:

 

 NOTE: 

Candela will determine the current draw of the product.

 

When calculating the total currents, use Table 2 to determine the highest value of RMS current 
for an individual appliance, then multiply these values by

 

the total number of appliances.

 

 Be 

sure  to  add  the  currents  for  any  other  appliances,  including  audible  signaling  appliances 
powered by the same source, and to include any required safety factors.

 

 

Table 1: Specification

 

Approvals

 

UL 1638A, ULC C22.2 No.205

 

Environmental

 

Indoor Use Only.

 

 0°C – 49°C (32°F – 120°F) 93% R.H.

 

Input Power

 

DC or FWR, 24V Regulated, 16 to 33V

 

Strobe Candela

 

15 cd, 30 cd, 75 cd, 110 cd (field selectable)

 

Horn Patterns

 

Temporal 4 high, Temporal 4 low, Continuous high, Continuous 
low (field selectable)

 

 

Table 2: Horn/Strobe Current Draw (mA RMS)

 

Strobe Candela Setting (cd)

 

16-33 Volts

 

 

Horn Strobe 

Current draw 

 

 

15 cd

 

 

30 cd

 

 

75 cd

 

 

110 cd

 

 

DC 

High Cont.

 

87mA

 

94mA

 

122mA

 

133mA

 

High T4 

80mA 

83mA 

108mA 

126mA 

Low Cont. 

74mA 

80mA 

110mA 

125mA 

Low T4

 

75mA

 

80mA

 

106mA

 

124mA

 

 

FWR

 

High Cont.

 

115mA

 

137mA

 

165mA

 

186mA

 

High T4 

113mA 

122mA 

154mA 

179mA 

Low Cont.

 

113mA

 

117mA

 

160mA

 

175mA

 

 

Low T4 

94mA 

117mA 

132mA 

160mA 

 

 

 

 

 
 

 

1 / 8

 

 
 

 

 

 

2 / 8

 

 
 

 

 

NOTE:

 These appliances were tested to the regulated voltage limits of 16.0-33.0 Volts.

 

 Do 

not apply voltage outside of this range.

 

 

NOTE:

 Check the minimum and maximum output of the power supply and standby battery 

and subtract the voltage drop from the circuit wiring resistance to determine the applied voltage 
to the strobes.

 

 The maximum wire impedance between strobes shall not exceed 35 ohms.

 

 

NOTE:

  Strobe  and  horns  are  not  designed  to  be  used  on  coded  systems  in  which  the 

applied voltage is cycled on and off.

 

 

NOTE:

 Make sure that the total rms (RMS) current required by all appliances that are connected 

to the system’s primary and secondary power sources, notification appliance circuits does not 
exceed the power sources’ rated capacity or the current ratings of any fuses on the circuits 
to which these appliances are wired.

 

 Overloading power sources or exceeding fuse ratings 

could result in loss of power and failure to alert occupants during an emergency, which could 
result in property damage and serious injury or death to you and/or others.

 

 

NOTE:

 The Temporal 4 pattern (0.1 second on, 0.1 second off, 0.1 second on, 0.1 second off, 

0.1 second on, 0.1 second off, 0.1 second on, 5 secs off and repeat) is specified by ANSI 
and NFPA 72 for standard emergency evacuation signaling.

 

 

WIRING, SETTINGS AND MOUNTING

 

The LED Horn Strobe and Horn appliance has 2 wiring terminals that accept two #12 to #18 
American Wire Gauge (AWG) wires at each screw

 

terminal.

 

 Strip leads 3/8 inches and connect 

to screw terminals.

 

Break all 2 wire runs on supervised circuits to ensure integrity of circuit supervision as shown 
in  Figure  2.

 

  The  polarity  shown  in  Figure  2,  the  wiring  diagram,  is  for  the  operation  of  the 

appliances. 

 

The polarity is reversed by the FACP during supervision.

 

 

NOTE:

 Wiring method shall be in accordance with CSA C22.1, Canadian Electrical Code, Part 1, 

Safety Standard for Electrical Installations, Section 32.

 

 

 NOTE: 

Do not fully back out terminal screws.

 

 

 NOTE:

 Horn setting Tone Selector switch is shown in Figure 3;

 

settings are T4 H, T4 L, CONT H, 

CONT L for Temporal 4 High, Temporal 4 Low, Continuous High, Continuous Low, 

respectively.

 

 

NOTE:

  Refer  Figure  4  to  connect  horn/strobe  with  standalone  detector  and  figure  5  for  Macurco 

control panels and synchronization module.

 

 

 

LIGHT OUTPUT:

 

 

 
 
 
 
 
 
 

 

 
Figure 2: LED Strobe and Horn Wiring

 

 
 
 
 
 

 

 

 

 

Figure 1: Horizontal and Vertical and Light Output

 

 

Figure 3: Candela and Tone Selector

 

 
 

FOR

 

Horn

 

Tone Selector

 

 
 

FOR

 

Strobe 

 

Candela Selector

 

HS-C

 

HS-A

 

HS-B

 

HS-R

 

Lamp=1 lm 

Max=837 650 cd/klm 

Power=9 In 

Multiply=0.001 

Degrees=90

 

Type C

 

0

 

100 000

 

200 000

 

300 000

 

400 000

 

500 000

 

600 000

 

700 000

 

Rect 95x70 mm

 

800 000

 

A. Legotin 
(C) 2004 

Lamp=1 lm 

Max=837 650 cd/klm 

Power=9 W 

Multiplier=0.001 

Degrees=360

 

Type C

 

0

 

100 000

 

200 000

 

300 000

 

400 000

 

500 000

 

600 000

 

700 000

 

Rect 95x70 mm

 

800 000

 

A. Legotin 
(C) 2004 

Reviews: