Macurco
TM
Macurco RD-24 Manual
REV
–
1.0.0
[34-8708-4770-1]
12
|
P a g e
Figure 4-3 Zone Add Relay Error
Figure 4-21
–
Zone Add Relay Error
4.3.1.2
Configure 4-20mA OUTPUT or Analog Output
Menu path: Main Menu-->CONFIGURE SYSTEM -->MANUAL CONFIGURE -->CONFIGURE ZONES -->ADD/EDIT ZONES--
>4-20MA OUTPUT: -->
NOTE: Assigning Analog Output - The panel has 3 onboard analog outputs so remote analog inputs start at 4.
Reference the Remote Device: I/O Chart at the end of this manual.
To assign 4-20mA outpu
t to a zone, select “4
-
20MA OUTPUT:” from the zone configuration menu and press ENTER.
Then select “OUTPUT NUMBER:” and press ENTER.
Figure 4-4
–
Zone 4-20mA Output Menu
Input the 4-20mA output number to assign it to the zone. The display will return to the 4-20 O/P menu screen and
show the currently assigned 4-20 mA output in the OUTPUT NUMBER field.
NOTE: A zone can be assigned only one 4-20mA output, and a 4-20mA output can only be assigned to one zone. 4-
20mA output once assigned to a zone can be re-assigned to a different zone or can be deleted from the zone.