20
IT
EN
FR
ES
• Before wiring the connector (
3
), unscrew and remove the central screw (
2
). Use the proper cable terminals (see figures
below).
NOTE:
Connector (
3
) wiring must be do ensuring a product rating of IP65;
• Wire the connector (
3
) with 3x0.75mm² cable for external Ø 6.2 to 8.1 mm. The cable to be used must be in double sheath,
suitable for outdoor use, with a minimum voltage of 500V and a temperature of at least 60 °C;
• Connect terminals 1 and 2 to the power supply and the earth cable to terminal ;
• Secure the connector (
3
) to the coil (
4
), tightening (recommended tightening torque 0.4 N.m ± 10%) the clamping screw (
2
);
• The valve needs to be connected to earth either through the pipe or through other means (ex. cable jumpers).
3.3 - INSTALLATION IN PLACES WHERE THERE IS THE RISK OF EXPLOSION (DIRECTIVE 2014/34/EU)
The solenoid valve is not suitable for use in zones here there is the risk of explosion.