XVP - XVPC.../NC
Madas Technical Manual
- 1|1.2aX - REV. 1 of 10
th
Sep 2020
2.0 - TECHNICAL DATA
• Use
: non-aggressive gases of the three families (dry gases)
• Ambient temperature (TS)
: -20 ÷ +60 °C
• Supply voltages (see table 2)
: 12 Vdc - 12 V/50 Hz - 24 Vdc - 24 V/50 Hz - 110 V/50-60 Hz - 230 V/50-60 Hz*
• Power supply tolerance
: -15% ... +10%
• Electric wiring
: electric cable l=3 metres with wire terminals
• No. cycles/hour
: see table 2a - 2b - 2c
• Absorbed power
: see table 2a - 2b - 2c
• Maximum operating pressure
: 200 mbar or 360 mbar (see product label)
• Opening time
: <1 s
• Closing time
: < 1 s
• Protection rating
: IP65
• Coil protection mode :
II 3G Ex mc ec nC IIC T4 Gc X - II 3D Ex mc tc IIIC T135°C Dc X
• Class
: A
• Mechanical resistance
: Group 2
• Rp Threaded connections
: (DN 15 - DN 20 - DN 25 - DN 32 - DN 40 - DN 50) according to EN 10226
• Flanged connections to be coupled with PN 16 flanges : (DN 25** - DN 32 - DN 40 - DN 50) ISO 7005 / EN 1092-1
• NPT threaded or ANSI 150 flanged connections : on request
• Filter element
: 1 mm wire mesh
• In compliance with
: Regulation (EU) 2016/426 (Appliances burning gaseous fuels)
EN 60079-0-7-14-15-18-31 - ATEX Directive 2014/34/EU
Directive EMC 2014/30/EU - Directive LVD 2014/35/EU
Directive RoHS II 2011/65/EU
* Only single-phase, the device does not work if powered with three-phase voltage.
** DN 25 with swivel flanges on request.
2.1 - MODEL IDENTIFICATION
XVP/NC - XVPC/NC :
Fast opening
ATEX 3G - 3D
XVPF/NC - XVPCF/NC :
Fast o flow adjustment
ATEX 3G - 3D
2.2 - SIL LEVEL
The SIL level of the stand-alone solenoid valve is SIL 2; when two solenoids are installed in series and the relative leak test
(Valve Proving System), certified according to EN 1643, the achieved level is SIL 3, as set forth in EN 676:2008. The solenoid
valve has PL d level. For further data refer to the SIL LEVEL table (table 3).
3.0 - COMMISSIONING THE DEVICE
3.1 - OPERATIONS PRIOR TO INSTALLATION
All installation operations must be carried out in the absence of an explosive atmosphere.
• It is necessary to close the gas upstream of the valve prior to installation;
• Make sure that the line pressure
DOES NOT EXCEED
the maximum pressure declared on the product label;
• Any protective caps (if any) must be removed prior to installation;
• Valve pipes and insides must be clear of any foreign bodies;
If the device is threaded:
• make sure that the pipe thread is not too long, to prevent damaging the body of the device when screwing it on;
If the device is flanged:
• make sure the inlet and outlet counter-flanges are perfectly coaxial and parallel in order to prevent unnecessary
mechanical stress to the body. Also calculate the space to insert the seal gasket;
• With regard to tightening operations, equip yourself with one or two calibrated torque wrenches or other controlled locking
tools;