2
7/16
M A D E L
SAFETY
The unit monitors the status of the dampers by means of LEDs, thereby indicating whether they are open
(green) or closed (red) or if there is an anomaly during normal operation or during the maintenance process
(flashing). This monitoring facilitates the location of any anomalies that might arise.
MAINTENANCE
Maintenance is performed using a push button on the unit, which activates the maintenance protocol. This
maintenance is performed in just a few minutes. The time spent physically at each one of the dampers is
also reduced.
By reducing the cost of the maintenance operations, it is possible to increase the frequency of these
operations, thereby substantially reducing the risk of incidents in case of a fire.
CE
mark EN 15650
•
In accordance with European Standard EN 15650:2010, regular maintenance inspections must be performed
periodically.
WIRING
The unit has a potential-free alarm input that receives the alarm signal generated by the fire detection
system. If this signal is activated, the dampers move to the safety position (closed).
Synchronisation with the fire alarm control panel facilitates maintenance and prevents interruptions to
operation of the building by reducing the maintenance time.
OPERATION/TASK
RESULTS
Damper reference
Inspection date
Check that the damper cables have not been damaged.
Verified with FDS-MINI
Check that the damper is clean, and clean if necessary.
In person
Check the condition of the slat and seals. Correct and record as necessary.
In person
Confirm the safety operation (closure) of the fire damper as per the attached instructions (PM01-….)
Verified with FDS-MINI
Confirm open and close operations through the control system and observe the process. Correct and record as
necessary. (For motorised dampers.)
Verified with FDS-MINI
Confirm the manual opening operation of the damper as per the attached instructions (PM02-…)
Confirm the opening and closing operation of the damper at the limit switches.
Correct and record as necessary. *For motorised dampers or dampers with the /–PIF/ accessory
Verified with FDS-MINI
Confirm that the damper returns to the normal working position.
Verified with FDS-MINI