OPERATING DEVICES
…-/MA/
Manual resetting damper. Automatic shooting by
means of a thermal fuse calibrated at 72
°
C.
Standard:
- Thermal fuse 72ºC
- Manual test button
- Manual resetting
- Position indicator
- IP42 protection
Optional:
…- /PIFR/
Closed switches device
1.
Plastic command cover
2.
Screws for cover attachment
3.
Manual test button
4.
Position indicator
5.
Manual resetting axe.
6.
Thermal fuse 72ºC
…- /M7F…V/
Damper operated by remote control by means
of an actuator with switch off device at 24 or
230V or a thermal fuse calibrated at 72
°
C.
Standard:
- Internal and external thermoelectrical
fuse 72ºC
- Automatic resetting
- Automatic closing by fuse 72ºC
- Remote closing by interruption of power
supply
- Manual test switch
- LED status fusible indicator
- Position damper indicator
- Closed switches
- IP54 Protection
1.
Actuator
2.
Position damper indicator
3.
Manual resetting
4.
Manual lock
5.
Plug closed switches cable
6.
Thermoelectrical fuse cable
7.
Power supply cable
8.
Thermoelectrical fuse 72ºC
9.
Manual test switch
10. LED status fusible indicator
1
2
2
3
4
5
6
fig. MA
2
1
8
4
3
5
7
6
10
9
fig. M7F
…V
fig. PIFR
90s / 15s
7Nm
CC 24V/ 48V
CA 24V
M7F24V
90s / 15s
7Nm
CA 230V
M7F230V
Time to
Open / Close
Voltage
90s / 15s
3.5W
7Nm
CC 24V/ 48V
CA 24V
M7F24V
90s / 15s
4.5W
7Nm
CA 230V
M7F230V
Torque
Reference
Consumption