background image

continue SETTING AND OPERATION

5.4 Running Capacity Setting

5.5 Timer mode

The pump’s on/off and running capacity could be commanded 

by timer, which could be programmed daily as needed. 

Maximum 4 timers can be set on the control panel.

Enter timer setting by pressing        .

Press        or          to set the local time.

When enter the timer-1 setting, the timer indicator 1 

will light up. “StA”will be shown on the screen. 

Press       to proceed and then press        or       to set the 

start time of timer-1 (with 30 minutes for each step), 

press       to con

rm.

Press        to confirm and move to timer-1 

When the start time of timer 1 is con

rmed, “End”will be 

shown on the screen. Press       to proceed and then 

press       or        to set the end time of timer-1 

(with 30 minutes for each step), press       to con

rm.

When the end time of timer 1 is con

rmed, “SPd”will be 

shown on the screen. Press         to proceed and then 

press        or        to set the running capacity of timer-1 

(30% - 100%, each step by 5%), press         to con

rm.

When the timer 1 setting is completed, repeat steps 3 – 5 

to complete the setting of timer 2 – 4.

Hold        for more than 3 seconds to read the 

real-time power.

Press       or        to set the running

 

capacity between

30%~100%, each step by 5%.

Press       to start. The pump will run at 80% of the 

running capacity at the initial startup after the 

self-priming.

NOTE:
When timer mode is acti

v

ated, if the set time period contains the 

current time, the pump will start running according to the set running 
capacity and the corresponding timer indicator (1 or 2 or 3 or 4) will 
stay on, and the set running capacity will be shown on the screen. 
If the set time period does not contain the current time, the timer 
indicator (1 or 2 or 3 or 4) that isabout to start running will light up
and flash, and the current time will be shown on the screen.
All 4 time periods should be set in chronological order. 
O

v

erlap setting of time will be considered in

v

alid, the pump will only 

run based on the pre

v

ious 

v

alid setting. 

During the timer setting, if users want to return to the pre

v

ious 

setting item, hold both                for 3 seconds. If users don’t need 
4 timers, they can hold        for 3 seconds after completing the 
setting of the speci

c timer, the system will automatically sa

v

e the 

current set 

v

alue and acti

v

ate the timer mode.

When the timer mode is on, users can check the setting of each timer. 
Press         to select the speci

c timer (1 or 2 or 3 or 4), and the 

corresponding timer indicator will light up. Then press        to check 
the start time, end time, and running capacity setting of the 
selected timer.

Users can hold         for 3 seconds to read the real-time power and 
exit timer mode by holding        for 3 seconds.
 

2

3

4

1

2

3

4

5

6

Hold        for more than 3 seconds to unlock the 
screen.

1

Note:

 

a. When the running capacity is adjusted, the system will sa

v

e the 

    latest parameter automatically.

b.When setting 100% speed, the pump will increase the speed 

   automatically if the pipeline resistance is high, but will not exceed 

   the rated power of each model. 

5.6 Parameter Setting

Description

Default 

Setting Setting Range

100%

 

2

80%

3

40%

 

4

 

100%

5

 

 

25

Restore factory setting.

Under off mode, hold both                for 

3 seconds.

Check the software 

v

ersion.

Under off mode, hold both                for 

3 seconds.

Manual priming.

Enable or disable the 

priming that occurs at 

start.

Backwash

 

capacity

25:enables

0:disables

80~100%, by 5% 

increments

30~100%, by 5% 

increments

30~100%, by 5% 

increments

30~100%, by 5% 

increments

Under ON mode, hold both                for 

3 seconds.

Enter parameter 
setting as shown.

Under OFF mode, hold both 

for 3 seconds to enter the parameter 

setting. The parameter address 

(on the left) and default setting 

v

alue 

(on the right) will flash alternately on 

the screen. Users can press       or   

to adjust the current 

v

alue, and hold 

both               for 3 seconds to the next 

parameter address. It will exit the 

parameter setting after 10 seconds 

without operation.

Parameter 

Address

6

INVER

FLOW

 

Self-priming/

 

2min

6

Self-primming 

recheck time

1-15min by 1min

increments

Digital input 2

Digital input 3

Digital input 4

For the purpose of 

backwashing, users can set a high running capacity 

according to the size of filter.

Summary of Contents for invermac inverFLOW INVFLO300

Page 1: ...Powered by INSTALLATION MANUAL...

Page 2: ...1 Tools required 4 2 Pump Location 4 3 Piping 4 4 Valve and Fittings 4 5 Check before initial startup 4 6 Application conditions 5 SETTING AND OPERATION 5 1 Display on control panel 5 2 Startup 5 3 S...

Page 3: ...L min Head Max m Circulation Power KW Power HP Flow at 8m L min Flow at 10m L min 2 TECHNICAL SPECIFICATIONS 3 OVERALL DIMENSION mm 4 INSTALLATION 3 Safety Goggles Gloves Philips Screwdriver Flathead...

Page 4: ...imization of the pool plumbing it is recommended to use a pipe with size of 50mm When installing the inlet and outlet tti i ngs f joints use the special sealant for PVC material 2 The dimension of suc...

Page 5: ...econds The pump will enter the default Manual Inverter mode at the initial startup If the user exits the self priming in the subsequent startup the pump will return to the previous state before the la...

Page 6: ...ing the timer setting if users want to return to the previous setting item hold both for 3 seconds If users don t need 4 timers they can hold for 3 seconds after completing the setting of the speci c...

Page 7: ...input 5 pin When PIN4 connect with PIN5 the pump will be mandatory to stop if disconnected the digital controller will be invalid When PIN3 connect with PIN5 the pump will be mandatory to run at 100 i...

Page 8: ...Low Water Flow Power Supply fault disconnected or defective wiring Fuses blown or thermal overload open Check the rotation of the motor shaft for free movement and lack of obstruction Because of long...

Page 9: ...cycling the packaging reduces the use of raw materials in the manufacturing process and also reduces the amount of waste in land ll sites Ensure that any plastic wrappings bags etc are disposed of saf...

Page 10: ...1 19 Cross recess head screw 3 5 O ring for Transparent Lid 128 5 3mm 1 20 Motor 1 6 Transparent Lid 1 21 Base 1 7 Nut for lid 1 22 Sealplate 1 8 Drain plug 2 23 Mechanical seal 1 9 O ring 10 3mm 2 24...

Page 11: ...ondition or warranty that cannot be legally excluded in relation to the supply of goods and services is limited to one of the following options Repairing the goods Replacing the goods with equivalent...

Page 12: ...AG045 DE 05...

Reviews: