background image

16

Reference & Installation Manual

Intellizone Delay Timer

Section [065]: 010 to 255 seconds; Default = 48 seconds

Enter the desired 3-digit value into section [065] to program 
the Intellizone Delay Timer.

Delay Before Alarm Report Code Transmission

Sections [001] to [016]: Zones 1 to 16; option [7]

Option [7] OFF =Delay alarm transmission disabled (default)
Option [7] ON =Delay alarm transmission enabled

This feature is commonly used with Entry Delay zones to reduce 
false alarms created by new users who may not disarm the 
system in time. This feature works as follows: 

When an alarm condition occurs on a zone with this option 
enabled, the console enables the bell/siren output, but does 
not report the alarm to the central station until the end of the 
Alarm Before Transmission Delay. 

During this period, disarming the system disables the bell/
siren output and cancels the report code transmission. 

Alarm Transmission Delay

Section [075]: 001 to 255 seconds; 000 = Disabled; Default = 0 
seconds

Enter the desired 3-digit delay value into section [075] to 
program the Alarm Transmission Delay.

Remote Panic Disarm Lock Delay

Section [078]: 001 to 255 seconds; 000 = Disabled; Default = 20 
seconds

When a panic alarm is generated through the use of a remote 
control, the system cannot be disarmed by remote control during 
the Remote Panic Disarm Lock Delay.

Enter the desired 3-digit delay value into section [078] to 
program the Remote Panic Disarm Lock Delay.

Force Zones

Sections [001] to [016]: Zones 1 to 16; Option [8]

Option [8] OFF =Force zone disabled
Option [8] ON =Selected zone is Force enabled (default)

Any open Force zones at the time of arming will be considered 
deactivated by the console. If during this period a deactivated 
zone is closed, the console will revert that zone to active status. 
Consequently, the console will generate an alarm if the zone is 
breached.

Fire zones cannot be programmed with the Force Zone 
option because the console will not bypass a Fire zone when 
the system is being Force armed.

Stay Delay Zones

Section [094]: Options [1]

Option [1] OFF =Stay Delay zone disabled (default)
Option [1] ON =Stay Delay zone enabled

When a Stay Delay zone is armed using the Stay or Instant 
arming methods and the zone is triggered, an alarm will not 
generate until the programmed Stay Delay elapses. A zone 
defined as Stay Delay 1 follows the Entry Delay 1 Timer of its 
assigned partition. Likewise, a zone defined as Stay Delay 2 

follows the Entry Delay 2 Timer of its assigned partition. To 
program the Entry Delay Timers, refer to Entry Delay 1 and Entry 
Delay 2 on page 13. 

Zones 15 and 16 become Hardwire Zones

Section [095]: Options [1] and [2]
Option [1] OFF = Wireless zone 15 remains unchanged (default)
Option [1] ON =

Wireless zone 15 uses the on-board hardwire 
zone input 1

Option [2] OFF = Wireless zone 16 remains unchanged (default)
Option [2] ON =

Wireless zone 16 uses the on-board hardwire 
zone input 2

The Magellan console comes with two on-board zone inputs, 
hardwire zone inputs 1 and 2. Section [095] options [1] and [2] 
allow you to convert zones 15 and 16 from wireless to hardwire 
by allowing you to connect hardwire detection devices (i.e. door 
contact) to zone inputs 1 and 2.

With section [095] option [1] ON, zone 15 is connected to 
zone input 1. 

With section [095] option [2] ON, zone 16 is connected to 
zone input 2.

EOL (End-Of-Line) Zones

Section [095]: Option [3]
Option [3] OFF = Hardwire zones 1 & 2 do not require EOL 

resistors (default)

Option [3] ON =

Hardwire zones 1 & 2 require EOL resistors

This feature only applies to Magellan’s on-board zone 
inputs. Section [095] options [1] and/or [2] (see Zones 15 
and 16 become Hardwire Zones on page 16) must be ON in 
order to use this feature.

If the hardwire detection devices connected to Magellan’s zone 
inputs 1 and 2 have input terminals that require 1K

9

 end of line 

resistors, enable (ON) section [095] option [3]. For details on 
using EOL resistors, refer to page 8.

Summary of Contents for MG-6060

Page 1: ...All In One Wireless Security System V1 0 Model MG 6060 Reference and Installation Manual...

Page 2: ......

Page 3: ...es to Stay Arming 20 Regular Arming Switches to Force Arming 20 Stay Arming Switches to Force Arming 20 Timed Auto Arming 20 No Movement Auto Arming 20 Auto Arming Options 20 One Touch Arming 21 Exit...

Page 4: ...2 Reference Installation Manual Panel Answer Options 33 Panel Identifier 33 PC Password 33 PC Telephone Number 33 Call Back Feature 33 Appendix 1 Ademco Contact ID Report Code List 34 Index 37...

Page 5: ...you read this entire manual before you begin installation Conventions Specifications Power input AC 9Vac 1A 9VA transformer or 16 5Vac 20VA transformer or DC 12Vdc to 18Vdc power supply Current consu...

Page 6: ...immediately access the Zone Profile menu For more in depth programming of the console s communication features see Reporting and Dialer Settings on page 24 4 Adding and Programming Zones 1 From the Zo...

Page 7: ...y 2 Press NEXT until you reach the Time and Date menu and press OK or press the 3 key to access the Time and Date menu 3 Select the time format 12Hr clock or 24Hr clock and then program the time Press...

Page 8: ...to a telephone line by connecting the telephone company s wires directly to Magellan s dialer or by connecting a standard 4 pin RJ 11 cable between the LINE plug of the console to a standard telephone...

Page 9: ...lug Connection Programmable Outputs PGMs Magellan comes equipped with two 50mA solid state PGM outputs When a specific event occurs in the system a PGM can be programmed to activate lights garage door...

Page 10: ...Software for Windows WinLoad allows for remote or on site uploading and downloading using most standard modems It also allows for advanced printing of reports and supports several languages simultaneo...

Page 11: ...lation near or in the path of strong RF fields i e neon lights computers and on or near metal objects circuit breakers boxes air conditioners and heater ducts since they may cause interference and red...

Page 12: ...with Magellan are two plastic feet as well as two rubber stops The plastic feet raise the Magellan console to a slight angle for easy viewing while the rubber stops prevent the console from sliding wh...

Page 13: ...ection s options are set When the options are set press the key to save and advance to the next section Press the key twice to exit without changing any data Programming Using a Paradox Memory Key The...

Page 14: ...to program all features options and commands except for the console s communication settings sections 100 to 154 as well as any user code The Maintenance code can be 4 or 6 digits in length see User C...

Page 15: ...16 3 digit 002 Entry Delay 2 zones are identical to the Entry Delay 1 zones see Entry Delay 1 on page 13 except it uses a separate Entry Delay Timer Entry Delay 2 Timer Section 061 001 to 255 seconds...

Page 16: ...d bell siren output signal as shown in Figure 17 on page 14 Figure 17 Bell Siren Output during a Fire Alarm Delayed Fire Zones Sections 001 to 016 Zones 1 to 16 3 digit 008 When a Delayed 24Hr Fire Zo...

Page 17: ...Option 2 OFF Bypass option disabled Option 2 ON Selected zone is bypass enabled default When a user uses the Bypass Programming feature only zones with the Bypass option enabled can be programmed as b...

Page 18: ...breached Fire zones cannot be programmed with the Force Zone option because the console will not bypass a Fire zone when the system is being Force armed Stay Delay Zones Section 094 Options 1 Option 1...

Page 19: ...e pushbutton is pressed Magellan will in turn become a doorbell and play a predetermined tone see Wireless Doorbell Tones on page 17 Please refer to the appropriate Magellan Wireless Door Contact Inst...

Page 20: ...rogrammed to perform up to 5 different actions Each digit in sections 161 to 176 represents a button or combination of buttons see Table 4 on page 18 To program a remote control s buttons 1 Access the...

Page 21: ...de 5 Future use D Turn FM radio ON OFF 6 Future use E FM radio memory scan 7 Future use F Paramedic alarm Inset 1 Removing the Battery Inset 2 Inserting the New Battery Step 1 Step 2 WARNING Damage to...

Page 22: ...g report code programmed in section 124 Example To automatically arm the system everyday at 6 15PM enable section 092 option 1 to activate Timed Auto arming and then key in 18 15 into section 085 Auto...

Page 23: ...the system is armed with a remote control Exit Delay Termination Section 093 Option 6 Option 6 OFF Exit delay termination feature disabled Option 6 ON Exit delay termination feature enabled default Wh...

Page 24: ...ypassed zone When option 5 is OFF the Tamper Recognition feature page 22 will follow the zone s bypass definition This means the console will ignore any tampers that occur on a bypassed zone Check in...

Page 25: ...econds See Table 7 on page 23 for the appropriate panic alarm keys Whether these panic alarms will generate a silent or audible alarm is determined by section 091 options 4 to 6 see Panic Alarm Types...

Page 26: ...s Section 125 One touch Arming The system was armed using a One touch Arming feature see page 21 Remote Arming The system was armed using the WinLoad software Future use Future use Disarming Report Co...

Page 27: ...d or battery voltage is d less than or equal to 6 9V Timer Loss The console has detected a loss in time or clock failure Section 150 Future use Fail To Communicate The Magellan console has failed all...

Page 28: ...e Installer menu Refer to the Magellan Quick Setup Guide for more information to play a pre recorded message to an external telephone or cellular telephone Please note the following when programming a...

Page 29: ...ndard messages and report codes Event Call Direction Section 100 Options 1 to 3 Arming Disarming Option 1 ON Call CSTN 1 Option 2 ON Call CSTN 2 Option 3 ON Call Pager telephone number Section 100 Opt...

Page 30: ...an console switches from tone DTMF dialing to pulse dialing on the fifth attempt to report events to the Central Monitoring Station The console continues to use pulse dialing until it establishes comm...

Page 31: ...tion 149 after the Power Failure Report Delay period has elapsed Disarm Reporting Options Section 093 Option 5 Option 5 OFF Always Report Disarming Option 5 ON Report Disarming only after Alarm Defaul...

Page 32: ...programmed period elapses see PGM Delay on page 30 If using the PGM Delay sections 087 and 089 can be used as a second PGM Activation Event For the Event List see the PGM Table in the Magellan Program...

Page 33: ...ngs Time Section 096 Option 5 Option 5 OFF Daylight savings time disabled default Option 5 ON Daylight savings time enabled With section 096 option 5 ON Magellan adjusts the system s clock time for da...

Page 34: ...lan console has failed to contact the monitoring station Fail to Communicate with Voice Reporting The Magellan console has failed to contact telephone number programmed for Voice reporting Fail to Com...

Page 35: ...le will answer the call You must wait at least 10 seconds before attempting the second call or Magellan will think it is the same call Panel Identifier Section 108 4 digit Hexa decimal number from 000...

Page 36: ...rigeration 27 153 Loss of heat 28 CID Reporting Code Programming Value 154 Water leakage 29 155 Foil break 2A 156 Day trouble 2B 157 Low bottled gas level 2C 158 High temperature 2D 159 Low temperatur...

Page 37: ...nance alert 7A Open Close 400 400 Open Close 7B 401 Open Close by user 7C 402 Group open close 7D 403 Automatic open close 7E 406 Cancel 7F 407 Remote arm disarm 80 CID Reporting Code Programming Valu...

Page 38: ...trigger test BD 602 Periodic test report BE 603 Periodic RF transmission BF 604 Fire test C0 605 Status report to follow C1 606 Listen in to follow C2 607 Walk test mode C3 608 Periodic test system t...

Page 39: ...131 to 134 24 135 to 138 24 139 24 140 12 24 25 141 to 144 25 145 to 148 25 149 25 150 25 151 25 153 25 154 12 25 155 25 156 25 161 to 176 18 180 31 181 12 182 12 187 14 190 14 200 12 201 31 24Hr zon...

Page 40: ...Key 9 10 PGMs 7 Telephone Line 6 UIP 256 8 WinLoad 8 X10 9 Console account number 26 Console audible trouble warning 31 Console tamper supervision 31 Console telephone numbers 25 Contact ID 27 Cut of...

Page 41: ...rings 33 O Options zone Alarm types 15 Auto zone Shutdown 15 Bypass option 15 Delay before Alarm Report Code Transmission 16 Force Zones 16 Intellizone 15 Overview zone programming 13 P Pack backup ba...

Page 42: ...es Follow Stay Zones 14 Instant Stay Zones 14 Supervision Check in 22 Console tamper 31 Wireless transmitters 22 Supervision Bypass options 22 Switch to Pulse dialing 28 System master code 12 System m...

Page 43: ...come hardwire 16 Wirless doorbell tones 17 X X10 connections 9 X10 PGM option 30 Z Zone alarm report codes 24 Zone alarm restore report codes 24 Zone definitions 24Hr Burglary Zones 14 24Hr Buzzer Zon...

Page 44: ...42 Reference Installation Manual...

Page 45: ...ediate disconnection of terminal equipment Standard jacks shall be so arranged that if plug connected thereto is withdrawn no interference to operation of equipment at customer s premises which remain...

Page 46: ......

Page 47: ......

Page 48: ...780 Industriel Blvd Saint Eustache Quebec J7R 5V3 CANADA Tel 450 491 7444 Fax 450 491 7313 www paradox ca Printed in Canada 09 2004 MAGELLAN EI01...

Reviews: