background image

Page 4 of 20

507389-02

Issue 1733

Installing without a Wall Sleeve

Refer to the following directions and Figure 1 for guidance 

in installing the unit without a wall sleeve:

1. 

Measure the size of the unit and provide an opening 

in an outside wall that will accept the unit. Local 

ordinances may require a steel lintel to support the 

wall above the opening. The opening must be square 

in all four corners.

2.  Position the unit so that the grilles on the outside face 

of the unit are flush or extend beyond the face of the 

exterior wall, but not recessed more than 2” from the 

face of the building. Provide a support under the unit, 

inside the building. Make sure that the inside support 

does  not  block  the  return  air.  The  unit  should  be 

installed level or pitched slightly to the outside of the 

building so that rain water will drain away.

3.  Seal the space between the unit and building opening 

using a non-hardening caulking compound. The seal 

must be weather-tight to prevent entrance of moisture 

and water into the building. Make sure the drain holes 

in the base are not plugged with caulking.

Evaporator Condensate Drain

Install the plastic drain tube (furnished) over the 5/8” O.D. 

fitting  in  the  center  of  the  Evaporator  condensate  pan. 

Connect other end of the drain tube to the open trap (see 

Figure 2). The plastic drain connection is provided so that 

it may be disconnected from the permanent drain tubing in 

the building in the event it becomes necessary to remove 

the cooling chassis assembly.

The drain line should pitch gradually downward at least 1” 

per 10’ of horizontal run to the open drain trap.

Be certain that the plastic drain tube has free drainage and 

is not crimped or flattened at any bend.

Figure 2. HWC Evaporator Condensate Drain 

Installation

Drain Pan

Open Drain Trap

Return 

Air Duct

To Open 

Drain Trap

Alternative 

Method

5/8

" I.D.

Plastic Tube

(Supplied)

Top of Drain Tube

Must be Below

Bottom of Drain Pan

Drain Tube - Pitch 1" 

for every 10 ft.

(Field Supplied)

Furnace Condensate Drain

The HWC9 furnace is provided with an internal condensate 

drain and drain fitting. A street elbow, a hose barb and a 

spigot adapter for connection to the drain fitting are factory-

supplied in the manual bag. All other piping is field-supplied 

to suit the installation and local codes.

If the furnace is installed in an unconditioned space, the 

condensate drain elbow outside the unit cabinet must 

have heat tape suitable for PVC pipe installed, and the 

elbow  insulated.  This  heat  tape  and  insulation  are  field-

supplied from standard hardware items that are available 

locally, and they must be installed in accordance with the 

instructions provided by their manufacturers.

Units are shipped with the drain fitting installed for side-exit 

condensate drainage. The drain fitting can be repositioned 

for front-exit condensate drainage if desired. Do not 

relocate or remove the internal condensate trap.

If unit will be started immediately upon completion of 

installation, the drain must be primed as described in the 

procedure outlined in the “Start-up” section.

Field-installed piping from the furnace must slope downward 

a minimum of 1/2” per foot toward the floor drain.

Piping for Side-Exit Condensate Drain

Determine whether the installation better suits a side-exit or 

a front-exit furnace condensate drain. For side condensate 

drain, see Figure 3 for component locations and additional 

details. A 2” clearance to the cabinet side is required for 

service access to the condensate drain fitting when using 

the side location.

1.  Install the factory-supplied street elbow to the drain 

fitting  by  threading  into  place.  Use  a  thread  sealant 

suitable for PVC; do not use thread tape.

2.  Use the appropriate primer and solvent cement to 

bond field-supplied drain line piping or fittings to the 

PVC street elbow. Do not use copper tubing or existing 

copper condensate lines for drain line.

3. 

Route the piping to an open floor drain. Do not connect 

directly to evaporator condensate drain line.

Piping for Front-Exit Condensate Drain

For front condensate drain, see Figure 4 for component 

locations and additional details. Use the factory-supplied 

hose barb with field-supplied flexible tubing or spigot and 

hose coupling for these installations. A 2” or 4”(depending 

of  choice  of  fittings)  clearance  to  the  cabinet  front  is 

required for service access when using the front location. 

The  modifications  necessary  to  convert  to  front-exit 

condensate drain are:

1. 

Disconnect the lower drain hose from the drain fitting.

2. 

Remove  the  screw  securing  the  drain  fitting  to  the 

division panel.

3. 

Remove the drain fitting and rotate it so that it faces 

the front of the furnace.

4.  Replace the securing screw.
5.  Disconnect lower drain hose from drain trap and rotate 

the hose so that the angled end will connect to the 

drain fitting in its new orientation.

Summary of Contents for HWC9 V-Series

Page 1: ...in the vicinity of this or any other appliance Such actions could result in property damage personal injury or death WARNING Do not store combustible materials near the furnace or warm air ducts The m...

Page 2: ...r portions of the unit may be surrounded by a closet with minimum clearances to combustible material of 0 sides 2 top and 1 front and plenum Adequate clearance must be provided to install gas line uni...

Page 3: ...tion air requirements during construction The furnace heat exchanger components duct system air filters and evaporator coils must be thoroughly cleaned following final construction clean up All furnac...

Page 4: ...led in an unconditioned space the condensate drain elbow outside the unit cabinet must have heat tape suitable for PVC pipe installed and the elbow insulated This heat tape and insulation are field su...

Page 5: ...ate Drain Component Locations Side Exit Figure 4 Furnace Condensate Drain Component Locations Front Exit Condensate Trap Side Panel Upper Drain Hose from Collector Box Lower Drain Hose to drain fittin...

Page 6: ...art of the appliance The venting system must not be modified or added on to The unit contains a combustion inducer The inducer draws the combustion products out of the heat exchanger and forces them f...

Page 7: ...must be used Do not use a connector which has previously serviced another gas appliance A manual shutoff valve must be located outside the unit The use of a union located upstream of the controls is...

Page 8: ...ional Electrical Code ANSI NFPA No 70 latest edition for installations in the U S or the Canadian Electrical Code Part 1 CSA C22 1 latest edition for installations in Canada See rating plate for minim...

Page 9: ...6 deep Insert the duct into the return opening in the bottom of the unit and flange the duct over the existing flanges around the opening inside the unit Make sure that all sides of the duct are flang...

Page 10: ...615 47 590 49 565 51 TAP 2 HEAT 208 or 230 780 37 755 38 730 39 710 40 TAP 3 HEAT 208 or 230 900 32 875 33 855 34 835 34 TAP 4 COOL 208 or 230 605 575 545 520 TAP 5 COOL 208 or 230 650 615 585 555 HWC...

Page 11: ...615 N A 590 N A 565 N A TAP 2 HEAT 208 or 230 780 61 755 63 730 65 710 67 TAP 3 HEAT 208 or 230 900 53 875 54 855 55 835 57 TAP 4 COOL 208 or 230 800 775 755 735 TAP 5 COOL 208 or 230 880 860 835 815...

Page 12: ...ode A high altitude conversion kit available from the manufacturer and approved for this purpose must be used Installation and Operation in Extremely Cold Weather Areas In areas where extremely cold b...

Page 13: ...satisfied the burners and combustion blower shut off 7 Circulating air blower will shut off 120 seconds later If the burners should fail to ignite the ignition control will try to ignite the burners...

Page 14: ...ly Igniter Combustion Inducer Gas Valve Gas Manifold Rollout Switch Burner Manifold Assembly Primary Limit Heat Exchanger Access Panel Cold End Header Box Upper Drain Hose Inducer Elbow Flue Tube Drai...

Page 15: ...Page 15 of 20 507389 02 Issue 1733 Figure 11 Burner Manifold Assembly Removal Step 7 Mounting Brackets Step 8 Burner Manifold Assembly Step 9 Step 10...

Page 16: ...m the vest panel 10 Finally pull the assembly from the unit 11 Once the burner assembly is removed the burners can be cleaned using a bottle brush 12 For reassembly follow the above steps in reverse o...

Page 17: ...urner assembly 3 Remove the orifices by unscrewing them Do not use any pipe thread sealant during reassembly 4 For reassembly follow the above steps in reverse order Combustion Inducer The combustion...

Page 18: ...Heater 1 Remove the control board mounting bracket as described previously 2 Remove the furnace condensate drain and upper and lower hoses as described previously 3 Disconnect the two lead wires at th...

Page 19: ...ing chassis normally requires no maintenance since it is a closed self contained system System is charged with R410A refrigerant Periodic maintenance is limited to Cleaning the air filter Follow direc...

Page 20: ...GERANT HIGH PRESSURE SWITCH BLUE BLK WHT RED BLACK BLACK BLUE YELLOW OPERATING MODE CIRCUIT HEATING R W COOLING R G Y FAN R G ORG GREEN WHITE WHITE GREEN N G L C BLACK BLUE GREEN BLK WHT COOL HEAT UNU...

Reviews: