background image

Page 12 of 18

508196-01

Issue 2120

Maintenance

Disconnect all electrical power to the unit before 

conducting any maintenance procedures. Failure to 

disconnect the power could result in personal injury or 

death.

 WARNING

The refrigeration system normally requires no maintenance 

since it is a closed, self-contained system. 

Periodic inspection and maintenance normally consists of 

changing or cleaning filters and (under some conditions) 

cleaning the coils.

Filter

Inspect the filter once a month. Replace disposable filter or 

clean the washable filter as necessary (a minimum of three 

times each heating or cooling season is recommended).

To clean the washable filter, shake filter to remove excess 

dirt and/or use a vacuum cleaner. Wash filter in soap or 

detergent water and replace after filter is dry. 

Motors

The indoor and outdoor fan motors are permanently 

lubricated and require no maintenance.

Outdoor Coil

Foreign material should not be allowed to accumulate on 

the outdoor coil surface or other parts in the air circuit. 

Cleaning should be as often as necessary to keep the coil 

clean. To clean the coil, remove the lower access panel 

and blow out debris by using compressed air or water. 

Be 

sure  power  to  unit  is  shut  off  before  using  water  to 

clean the coil.

Care should be used when cleaning the coils so that 

the coil fins are not damaged.

Primary and Secondary Condensate Drain

Foreign material should not be allowed to clog the drain 

hole. Inspect and clear drain opening prior to each heating 

and cooling season.

The defrost control is also equipped with a set of pins to 

aid in the troubleshooting of the defrost system (see Figure 

11). The following is a brief outline of the testing of the 

defrost system.

1.  Defrost sensor must be closed, 32°F or below. If 

temperatures are such that the switch will not close, 

jumper between defrost sensor terminals on the 

defrost control.

2.  Start system in heating operation.
3.  Place the defrost pin jumper on the test pins for a brief 

second, then place back on the proper defrost time 

setting (30, 60, or 90). This will speed up defrost time 

interval as shown in Table 7.

Defrost Control Setting

Defrost Test Cycle Time

30 minutes

7 seconds

60 minutes

14 seconds

90 minutes 

21 seconds

Table 7. Defrost Test Cycle Time

The reversing valve will then shift to defrost mode and 

the outdoor fan should stop. After 2 seconds of defrost 

operation, the reversing valve should shift back to heating 

operation and the outdoor fan should start.

Diagnostic LEDs

The state (Off, On, Flashing) of two LEDs on the defrost 

board (DS1 [Red] and DS2 [Green]) indicate diagnostics 

conditions that are described in Table 8.

Mode

Green LED (DS2)

Red LED (DS1)

No power to control

Off

Off

Normal operation / 

power to control

Simultaneous slow flash

Timed lockout

Alternating slow flash

Low pressure switch 

fault

Off

Slow flash

Low pressure switch 

lockout

Off

On

High pressure switch 

fault

Slow flash

Off

High pressure switch 

lockout

On

Off

Table 8. 

Summary of Contents for MHP4-12 Series

Page 1: ...llation These units are not approved for mobile home applications Such use could result in property damage personal injury or death WARNING General These instructions explain the recommended method of installation of the MagicPak All In One HVAC system model MHP4 electric cooling unit and associated electrical wiring These instructions and any instructions packaged with mating components and or ac...

Page 2: ...e carrier s freight bill Take special care to examine the unit inside the carton if the carton is damaged File a claim with the transportation company If any damage is discovered and reported to the carrier do not install the unit as claim may be denied Check the unit rating plate to confirm specifications are as ordered Limitations The unit should be installed in accordance with all national and ...

Page 3: ...imension B represents the height of the optional front return air duct opening J Return Air Opening K M Thermostat Wiring Connections Line Voltage Knockouts 7 8 and 1 1 8 Dia Top View 3 4 H 2 1 4 5 Supply Air Opening 1 6 1 16 28 H 6 1 8 Side View D A N Outdoor Fan Discharge Outdoor Coil F G E Rear View Return Air Opening Supply Air Opening Ventilation Air Chase Secondary Condensate Drain Pan 3 4 N...

Page 4: ...ury or death Accessibility Clearances The front of the unit must be accessible for service A minimum clearance of 30 in front of unit is required for service If the unit is enclosed a door or access panel aligned with the front of the unit is the preferred method of providing access The door or access panel opening must be a minimum of 30 wide centered on the unit and be as tall as the unit Supply...

Page 5: ...ASLEEVE 5 Orientation of Flange Two Positions Three Positions MHP4 12 09 12 Lower Lower Down MHP4 12 18 Up MHP4 12 24 30 Upper Middle MHP4 14 36 N A Upper Table 2 4 Place the unit into the wall sleeve Lift leading end of unit and walk unit onto the sleeve Once in the wall sleeve lower the unit into position This prevents damage to the base pads Assure that the unit is level and completely seated a...

Page 6: ...heck unit supply and return air outlets for debris before making ductwork connections It is recommended that supply and return duct connections at the unit be made with flexible joints If flexible ducts are used a 6 sheet metal starter collar is required The supply and return air duct systems should be fabricated per the designed CFM and static requirements of the job see Table 3 Ductwork should n...

Page 7: ...57 0 21 3 kW TAP 4 AUX HEAT 615 93 0 12 590 97 0 13 555 101 0 14 N A N A N A N A N A N A TAP 5 AUX HEAT 715 127 0 17 685 134 0 18 655 140 0 19 630 146 0 20 600 151 0 20 5 kW TAP 4 AUX HEAT 665 110 0 15 635 114 0 15 605 118 0 16 N A N A N A N A N A N A TAP 5 AUX HEAT 750 148 0 20 725 154 0 21 700 160 0 21 675 166 0 22 650 171 0 23 7 kW TAP 4 AUX HEAT 725 137 0 18 705 144 0 19 675 150 0 20 N A N A N...

Page 8: ...1260 315 0 42 1230 328 0 44 1200 338 0 45 N A Do not operate unit using this blower speed at this external static pressure As shipped speed for Cooling operation Blower speed must be field adjusted to Speed Tap 3 for higher duct static applications As shipped speed for Heating operation Blower speed must be field adjusted to Speed Tap 5 for higher duct static applications Table 3 Blower Performanc...

Page 9: ...he unit and the design will allow drainage out through the wall sleeve and louver to the outside of the building Use thread sealant on the threaded fittings Install threaded fittings by hand only Do not over torque the fittings Do not thread metal condensate fittings to unit drain pans CAUTION Ventilation Air Units ship with a panel installed that seals the return air compartment at the ventilatio...

Page 10: ...sulated wires 18 AWG should be used to connect the thermostat to the unit Electrical Connections The unit must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA No 70 latest edition or CSA C22 2 Part 1 latest edition Any alteration of internal wiring will void certification and warranty Units are factory wired for a...

Page 11: ...ter the thermostat is satisfied NOTE The 7 2 and 10 kW heats strips offer a W1 and W2 thermostat connection Taking advantage of the two heat strip circuits requires a 3 stage thermostat Y for heat pump W1 for electric heat stage 1 and W2 for electric heat stage 2 If a 2 stage thermostat is used pigtail W1 and W2 wires together when connecting the thermostat wires at the unit Defrost Cycle If the o...

Page 12: ...ate Drain Foreign material should not be allowed to clog the drain hole Inspect and clear drain opening prior to each heating and cooling season The defrost control is also equipped with a set of pins to aid in the troubleshooting of the defrost system see Figure 11 The following is a brief outline of the testing of the defrost system 1 Defrost sensor must be closed 32 F or below If temperatures a...

Page 13: ...all sleeve and louver accessories for safe operation Improper installations could result in property damage personal injury or death WARNING Refer to Table 9 for dimension information B 29 1 8 Required Wall Opening C Maximum Wall Thickness Exterior Wall 16 A 16 5 8 29 Wall Sleeve Figure 12 ...

Page 14: ...AL 7 32 3 4 32 7 8 8 ASLEEVE10 2 ASLEEVEXT4 2 ALVRP 2 ALVRAL 7 32 3 4 32 7 8 10 14 ASLEEVE12 2 ASLEEVEXT4 2 ALVRP 2 ALVRAL 7 32 3 4 32 7 8 12 16 ASLEEVE6 5 ALVRP 3 45 45 1 8 6 ASLEEVE8 5 ALVRP 3 45 45 1 8 8 ASLEEVE10 5 ASLEEVEXT4 3 ALVRP 3 45 45 1 8 10 14 ASLEEVE12 5 ASLEEVEXT4 3 ALVRP 3 45 45 1 8 12 16 ASLEEVE6 5 ALVRAL 3 ALVRALC 3 45 45 1 8 6 ASLEEVE8 5 ALVRAL 3 ALVRALC 3 45 45 1 8 8 ASLEEVE10 5...

Page 15: ...508196 01 Issue 2120 Page 15 of 18 Wiring Diagrams Figure 13 Wiring Diagram MHP with Single Circuit and Hard Start Enabled 0 75 Ton through 2 5 Ton ...

Page 16: ...Page 16 of 18 508196 01 Issue 2120 Figure 14 Wiring Diagram MHP with Dual Circuit and Hard Start Enabled 0 75 Ton through 2 5 Ton ...

Page 17: ...508196 01 Issue 2120 Page 17 of 18 Figure 15 Wiring Diagram MHP with Single Circuit 3 Ton ...

Page 18: ...Page 18 of 18 508196 01 Issue 2120 Figure 16 Wiring Diagram MHP with Dual Circuit 3 Ton ...

Reviews: