background image

508196-01

Issue 2120

Page 11 of 18

Operation

Sequence of Operation

Upon initial “power up” to unit, there is a 3-minute time delay 

to the compressor contactor (R to Y). Any 24V interrupt (R, 

C) to the defrost control will initiate the 3-minute delay to 

the contactor.

Cooling

When the thermostat is in the cooling mode, the O circuit 

is powered which energizes the reversing valve. Upon 

cooling demand, the thermostat closes circuit R to Y and 

G. Closing R to Y closes the unit contactor, starting the 

compressor and outdoor fan, and signaling the indoor 

blower to run at cooling speed. Upon satisfying cooling 

demand, the thermostat will open the above circuits and 

open the main contactor, stopping the compressor and 

outdoor fan. The unit is equipped with a blower OFF delay; 

the blower will continue to operate for a fixed 90 seconds 

after the thermostat is satisfied.

Heating

Upon heating demand, the thermostat closes circuit R to 

Y, which closes the unit contactor, starting the compressor 

and outdoor fan. The reversing valve is not energized in 

the heating mode. The Y signal from the thermostat brings 

the indoor blower on at heat pump speed. The second 

stage of the thermostat closes circuit R to W, which closes 

the unit sequencers, bringing the auxiliary electric heat on. 

The W signal from the thermostat brings the indoor blower 

on at electric heat speed. Upon satisfying heating demand, 

the thermostat opens the above circuits and stops unit 

operation. 

The unit is equipped with a blower OFF delay; the blower 

will continue to operate for a fixed 90 seconds (heat pump) 

or 120 seconds (electric heat) after the thermostat is 

satisfied.

NOTE: 

The  7.2  and  10  kW  heats  strips  offer  a  W1  and 

W2  thermostat  connection.  Taking  advantage  of  the  two 

heat strip circuits requires a 3-stage thermostat (Y for heat 

pump,  W1  for  electric  heat  stage  1,  and  W2  for  electric 

heat stage 2). If a 2-stage thermostat is used, “pigtail” W1 

and  W2  wires  together  when  connecting  the  thermostat 

wires at the unit.

Defrost Cycle

If the outdoor ambient conditions are such that frost forms 

on the outdoor coil, the defrost control monitors the need 

for, initiates, and terminates defrost cycles as necessary to 

maintain system performance. 

The defrost control is time/temperature initiated and 

temperature terminated with a maximum defrost time 

(time-out) of 14 minutes. The time between defrost cycles 

is preset at 90-minute intervals at the factory, but can be 

field  adjusted  to  30  or  60  minutes.  To  field  adjust  time 

between defrost cycles, place defrost time plug in the 

proper position (see Figure 11).

Figure 10. Defrost Control

24V TERMINAL

STRIP

CONNECTIONS

DIAGNOSTIC

LEDS

HIGH PRESSURE

SWITCH

TEST

PINS

REVERSING

VALVE

DEFROST

THERMOSTAT

LOW PRESSURE

SWITCH

SERVICE LIGHT

CONNECTIONS

FIELD SELECT 

DEFROST INTERVAL 

TIMING PINS

30

TEST

90

60

P1

Figure 11. Defrost Interval Timing Jumper

Defrost control will initiate a defrost cycle if the time period 

has elapsed and the defrost sensor sees a temperature 

below freezing. At the start of a defrost cycle, the defrost 

control will energize the reversing valve solenoid, shifting 

the reversing valve and de-energizing the outdoor fan. 

The defrost control will also energize auxiliary heat for 

increased comfort during defrost. The unit will remain in 

defrost until the defrost sensor has determined that the 

frost has been removed from the coil or a 14-minute time 

period has elapsed.

Summary of Contents for MHP4-12 Series

Page 1: ...llation These units are not approved for mobile home applications Such use could result in property damage personal injury or death WARNING General These instructions explain the recommended method of installation of the MagicPak All In One HVAC system model MHP4 electric cooling unit and associated electrical wiring These instructions and any instructions packaged with mating components and or ac...

Page 2: ...e carrier s freight bill Take special care to examine the unit inside the carton if the carton is damaged File a claim with the transportation company If any damage is discovered and reported to the carrier do not install the unit as claim may be denied Check the unit rating plate to confirm specifications are as ordered Limitations The unit should be installed in accordance with all national and ...

Page 3: ...imension B represents the height of the optional front return air duct opening J Return Air Opening K M Thermostat Wiring Connections Line Voltage Knockouts 7 8 and 1 1 8 Dia Top View 3 4 H 2 1 4 5 Supply Air Opening 1 6 1 16 28 H 6 1 8 Side View D A N Outdoor Fan Discharge Outdoor Coil F G E Rear View Return Air Opening Supply Air Opening Ventilation Air Chase Secondary Condensate Drain Pan 3 4 N...

Page 4: ...ury or death Accessibility Clearances The front of the unit must be accessible for service A minimum clearance of 30 in front of unit is required for service If the unit is enclosed a door or access panel aligned with the front of the unit is the preferred method of providing access The door or access panel opening must be a minimum of 30 wide centered on the unit and be as tall as the unit Supply...

Page 5: ...ASLEEVE 5 Orientation of Flange Two Positions Three Positions MHP4 12 09 12 Lower Lower Down MHP4 12 18 Up MHP4 12 24 30 Upper Middle MHP4 14 36 N A Upper Table 2 4 Place the unit into the wall sleeve Lift leading end of unit and walk unit onto the sleeve Once in the wall sleeve lower the unit into position This prevents damage to the base pads Assure that the unit is level and completely seated a...

Page 6: ...heck unit supply and return air outlets for debris before making ductwork connections It is recommended that supply and return duct connections at the unit be made with flexible joints If flexible ducts are used a 6 sheet metal starter collar is required The supply and return air duct systems should be fabricated per the designed CFM and static requirements of the job see Table 3 Ductwork should n...

Page 7: ...57 0 21 3 kW TAP 4 AUX HEAT 615 93 0 12 590 97 0 13 555 101 0 14 N A N A N A N A N A N A TAP 5 AUX HEAT 715 127 0 17 685 134 0 18 655 140 0 19 630 146 0 20 600 151 0 20 5 kW TAP 4 AUX HEAT 665 110 0 15 635 114 0 15 605 118 0 16 N A N A N A N A N A N A TAP 5 AUX HEAT 750 148 0 20 725 154 0 21 700 160 0 21 675 166 0 22 650 171 0 23 7 kW TAP 4 AUX HEAT 725 137 0 18 705 144 0 19 675 150 0 20 N A N A N...

Page 8: ...1260 315 0 42 1230 328 0 44 1200 338 0 45 N A Do not operate unit using this blower speed at this external static pressure As shipped speed for Cooling operation Blower speed must be field adjusted to Speed Tap 3 for higher duct static applications As shipped speed for Heating operation Blower speed must be field adjusted to Speed Tap 5 for higher duct static applications Table 3 Blower Performanc...

Page 9: ...he unit and the design will allow drainage out through the wall sleeve and louver to the outside of the building Use thread sealant on the threaded fittings Install threaded fittings by hand only Do not over torque the fittings Do not thread metal condensate fittings to unit drain pans CAUTION Ventilation Air Units ship with a panel installed that seals the return air compartment at the ventilatio...

Page 10: ...sulated wires 18 AWG should be used to connect the thermostat to the unit Electrical Connections The unit must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA No 70 latest edition or CSA C22 2 Part 1 latest edition Any alteration of internal wiring will void certification and warranty Units are factory wired for a...

Page 11: ...ter the thermostat is satisfied NOTE The 7 2 and 10 kW heats strips offer a W1 and W2 thermostat connection Taking advantage of the two heat strip circuits requires a 3 stage thermostat Y for heat pump W1 for electric heat stage 1 and W2 for electric heat stage 2 If a 2 stage thermostat is used pigtail W1 and W2 wires together when connecting the thermostat wires at the unit Defrost Cycle If the o...

Page 12: ...ate Drain Foreign material should not be allowed to clog the drain hole Inspect and clear drain opening prior to each heating and cooling season The defrost control is also equipped with a set of pins to aid in the troubleshooting of the defrost system see Figure 11 The following is a brief outline of the testing of the defrost system 1 Defrost sensor must be closed 32 F or below If temperatures a...

Page 13: ...all sleeve and louver accessories for safe operation Improper installations could result in property damage personal injury or death WARNING Refer to Table 9 for dimension information B 29 1 8 Required Wall Opening C Maximum Wall Thickness Exterior Wall 16 A 16 5 8 29 Wall Sleeve Figure 12 ...

Page 14: ...AL 7 32 3 4 32 7 8 8 ASLEEVE10 2 ASLEEVEXT4 2 ALVRP 2 ALVRAL 7 32 3 4 32 7 8 10 14 ASLEEVE12 2 ASLEEVEXT4 2 ALVRP 2 ALVRAL 7 32 3 4 32 7 8 12 16 ASLEEVE6 5 ALVRP 3 45 45 1 8 6 ASLEEVE8 5 ALVRP 3 45 45 1 8 8 ASLEEVE10 5 ASLEEVEXT4 3 ALVRP 3 45 45 1 8 10 14 ASLEEVE12 5 ASLEEVEXT4 3 ALVRP 3 45 45 1 8 12 16 ASLEEVE6 5 ALVRAL 3 ALVRALC 3 45 45 1 8 6 ASLEEVE8 5 ALVRAL 3 ALVRALC 3 45 45 1 8 8 ASLEEVE10 5...

Page 15: ...508196 01 Issue 2120 Page 15 of 18 Wiring Diagrams Figure 13 Wiring Diagram MHP with Single Circuit and Hard Start Enabled 0 75 Ton through 2 5 Ton ...

Page 16: ...Page 16 of 18 508196 01 Issue 2120 Figure 14 Wiring Diagram MHP with Dual Circuit and Hard Start Enabled 0 75 Ton through 2 5 Ton ...

Page 17: ...508196 01 Issue 2120 Page 17 of 18 Figure 15 Wiring Diagram MHP with Single Circuit 3 Ton ...

Page 18: ...Page 18 of 18 508196 01 Issue 2120 Figure 16 Wiring Diagram MHP with Dual Circuit 3 Ton ...

Reviews: