background image

Page 2 of 15

506325-01

Issue 1734

Installation

These units are not approved for mobile home 

applications. Such use could result in property damage, 

personal injury, or death.

 WARNING

General

These instructions explain the recommended method of 

installation of the MHP4 electric cooling unit and associated 

electrical wiring.

This unit is designed and approved for use as a self-

contained air-to-air air conditioning system.

These instructions, and any instructions packaged with 

mating components and/or accessories, should be carefully 

read prior to beginning installation. Note particularly any 

CAUTIONS

 or 

WARNINGS

 in these instructions and all 

labels on the units.

These instructions are intended as a general guide only, 

for use by qualified personnel and do not supersede any 

national or local codes in any way. Compliance with all local, 

state, provincial, or national codes pertaining to this type of 

equipment should be determined prior to installation.

Units that comply with the maximum cabinet leakage 2% of 

rated airflow requirements of ANSI/ASHRAE 193 (complies 

with IECC 2015) are identified on the rating plate.

Inspection

Upon receipt of equipment, carefully inspect it for possible 

shipping damage. If damage is found, it should be noted 

on the carrier’s freight bill. Take special care to examine 

the unit inside the carton if the carton is damaged. File a 

claim with the transportation company. 

If any damages 

are discovered and reported to the carrier do not 

install the unit, as claim may be denied.

Check  the  unit rating  plate  to  confirm  specifications 

are as ordered.

Table 1. Application Limitations

Outdoor Ambient Air Temperature °F

Minimum D B

Maximum D B

Cool 

Cool 

Heat

65

115

75

Indoor Ambient Air Temperature °F

Minimum 

Maximum

DB/WB

DB

DB/WB

DB

Cool

Heat 

Cool

Heat

62/57

50

90/72

80

DB = Dry Bulb
WB = Wet Bulb

Limitations

The unit should be installed in accordance with all national 

and local safety codes.

Limitations of the unit and appropriate accessories must 

also be observed.

The outdoor fan is designed to operate against no more 

than .10” w.c. static pressure.

Minimum and maximum operation conditions must be 

observed to assure maximum system performance 

with minimum service required. Refer to Table 1 for the 

application limitations of the unit.

Location

The unit must be installed with approved wall sleeve 

and grille accessories for safe operation. Improper 

installations could result in property damage, personal 

injury, or death.

 WARNING

For information on wall sleeves and grille accessories, see 

the 

Accessories

 section. 

The  design  is  certified  for  thru-the-wall  or  up-to-the  wall 

(inside wall) installation only. The interior portions of 

the unit may be surrounded by a closet with clearances 

to combustible material held to 0” at the sides, top, and 

front of the plenum. All servicing and cleaning of the unit 

can be performed from the front. If installed in a closet 

or utility room, provide 25” clearance in front for service 

if the door to the room is not in line with the front of the 

unit (see Figure 1). 

Accessibility clearances must take 

precedence over fire protection clearances.

Summary of Contents for MHP-10-24

Page 1: ...est edition in the United States the Canadian Electrical Code Part 1 CSA 22 1 latest edition in Canada and any state or provincial laws or local ordinances Local authorities having jurisdiction should...

Page 2: ...carrier do not install the unit as claim may be denied Check the unit rating plate to confirm specifications are as ordered Table 1 Application Limitations Outdoor Ambient Air Temperature F Minimum D...

Page 3: ...the unit is the preferred method of providing access The door or access panel must be at least 30 wide centered on the unit and as tall as the unit If a return duct is not installed in order to provi...

Page 4: ...nd the louver grille kit along with Figure 2 for guidance in assembling and installing the wall sleeve and louver grille The sleeve is not intended as the sole support for the unit An additional suppo...

Page 5: ...ecommended that supply and return duct connections at the unit be made with flexible joints If flexible ducts are used a 6 sheet metal starter collar is required The supply and return air duct systems...

Page 6: ...inches MHP 18 288 square inches MHP 24 384 square inches MHP 30 36 480 square inches 9 and 10 EER Models Condensate Drain Provisions must be made to properly drain the indoor and outdoor drain pans o...

Page 7: ...e contactor Cooling When the thermostat is in the cooling mode the O circuit is powered which energizes the reversing valve Upon cooling demand the thermostat closes circuit R to Y and G Closing R to...

Page 8: ...oting of the defrost system see Figure 8 The following is a brief outline of the testing of the defrost system 1 Defrost sensor must be closed 32 F or below If temperatures are such that the switch wi...

Page 9: ...air circuit Cleaning should be as often as necessary to keep the coil clean To clean the coil remove the lower access panel and blow out debris by using compressed air or water Be sure power to unit i...

Page 10: ...ASLEEVE 3 Wall Sleeve Kit 45 Louver MHP4 09 12 18 ASLEEVE2 1 2 Wall Sleeve Kit MHP4 09 12 18 24 30MHP4 10 18 24 ASLEEVE2 2 2 Wall Sleeve Kit MHP4 10 30 MHP4 09 36 ASLEEVE6 1 6 Wall Sleeve Kit MHP4 09...

Page 11: ...10 3 10 45 45 1 8 ASLEEVE10 4 10 45 45 1 8 ASLEEVE12 1 12 29 29 1 8 ASLEEVE12 2 12 32 3 4 32 7 8 ASLEEVE12 3 12 45 45 1 8 ASLEEVE12 4 12 45 45 1 8 ASLEEVE 3 45 45 1 8 Thru the wall installations only...

Page 12: ...ITOR RUN CONDENSER FAN COMP CONNECTOR BLOCK BLUE GREY COOLING R G Y O BLACK BLACK X FRmR X FRmC GRAY BROWN C H MH ML FUSE BLUE BLUE COM RVG RV O Y W R DFS2 DFS1 C C DF1 LIGHT BLUE REVERSING VALVE BLAC...

Page 13: ...SEQ C RVG CC O Y W R DFS DFS C TRANSFORMER REVERSING VALVE COIL DF DF DEFROST RELAY FAN MOTOR DUAL CAPACITOR CONTACTOR L1 T1 C R S 208 230V 1 60HZ DEFROST SENSOR DEFROST CONTROL BLOWER CONTROL COM 20...

Page 14: ...LING R G Y O BLACK BLACK X FRmR X FRmC GRAY BROWN C H MH L FUSE BLUE BLUE COM RVG RV O Y W R DFS2 DFS1 C C DF1 LIGHT BLUE REVERSING VALVE BLACK BLACK O O ORANGE WHITE RED BLACK BLACK DEFROST CONTROL B...

Page 15: ...IT SEQ C RVG CC O Y W R DFS DFS C TRANSFORMER REVERSING VALVE COIL DF DF FAN MOTOR DUAL CAPACITOR CONTACTOR L1 T1 C R S 208 230V 1 60HZ DEFROST CONTROL BLOWER CONTROL COM 208 240 24 V G CONTACTOR COIL...

Reviews: