background image

506325-01

Issue 1734

Page 5 of 15

Figure 3. Positioning Divider Panel

4.  Use the two installation brackets to secure the unit to 

the wall sleeve (see Figure 4). The units are shipped 

with the brackets placed in the return air compartment. 

Hook each bracket into the front edge of the wall sleeve 

side. Position the bracket so it can be bent around the 

front corner of the unit. Remove one of the two screws 

in that position on the unit. Line up one of the holes in 

the installation bracket with the screw hole and attach 

the bracket to the unit with that screw. Make sure to 

fasten tight enough that the seal is maintained. Trim 

off excess bracket if applicable.

5. 

Inspect the fit up of the unit to the wall sleeve. Verify 

that the gaskets of the wall sleeve make a complete 

seal to the unit paying particular attention to top and 

bottom corners of unit to sleeve seal. Caulk if needed.

Ductwork

Ductwork should be designed and sized according to the 

methods in Manual Q of the Air Conditioning Contractors 

of America (ACCA).

Check unit air supply outlet for debris before making 

ductwork connections.

It is recommended that supply and return duct connections 

at the unit be made with flexible joints. If flexible ducts are 

used, a 6” sheet metal starter collar is required.

The supply and return air duct systems should be designed 

for the CFM and static requirements of the job (see Table 

2). 

They should not be sized to match the dimensions 

of the duct connections on the unit.

 The return duct 

should be sealed to the unit casing (including the casing 

slots  for  aiding  filter  access)  and  terminate  outside  the 

space containing the unit.

Table 2. Blower Performance

Model 

Blower 

Speed

External Static Pressure (in. w.c. w/filter)

0.1

0.2

0.3

0.4

0.5

MHP4-09-12 

MHP4-09-18 

MHP4-09-24

Low

450

440

425

400

370

Medium/Low

700

690

680

650

600

Medium/High

810

800

790

770

730

High

940

920

875

850

810

MHP4-9-30

Low

620

600

580

560

535

Medium/Low 

840

820

785

750

700

Medium/High

975

940

870

825

760

High

1075

1000

930

880

800

MHP4-9-36

Low

750

720

680

650

620

Medium/Low

1000

980

950

920

880

Medium/High

1100

1080

1050

1020

980

High

1270

1230

1200

1170

1130

MHP4-10-18 

MHP-10-24

Low

450

440

425

400

370

Medium/Low

700

690

680

650

600

Medium/High

810

800

790

770

730

High

940

920

875

850

810

MHP4-10-30

Low

630

620

610

580

550

Medium/Low

900

890

850

800

750

Medium/High

1070

1030

1000

920

840

High

1220

1150

1100

1030

920

Summary of Contents for MHP-10-24

Page 1: ...est edition in the United States the Canadian Electrical Code Part 1 CSA 22 1 latest edition in Canada and any state or provincial laws or local ordinances Local authorities having jurisdiction should...

Page 2: ...carrier do not install the unit as claim may be denied Check the unit rating plate to confirm specifications are as ordered Table 1 Application Limitations Outdoor Ambient Air Temperature F Minimum D...

Page 3: ...the unit is the preferred method of providing access The door or access panel must be at least 30 wide centered on the unit and as tall as the unit If a return duct is not installed in order to provi...

Page 4: ...nd the louver grille kit along with Figure 2 for guidance in assembling and installing the wall sleeve and louver grille The sleeve is not intended as the sole support for the unit An additional suppo...

Page 5: ...ecommended that supply and return duct connections at the unit be made with flexible joints If flexible ducts are used a 6 sheet metal starter collar is required The supply and return air duct systems...

Page 6: ...inches MHP 18 288 square inches MHP 24 384 square inches MHP 30 36 480 square inches 9 and 10 EER Models Condensate Drain Provisions must be made to properly drain the indoor and outdoor drain pans o...

Page 7: ...e contactor Cooling When the thermostat is in the cooling mode the O circuit is powered which energizes the reversing valve Upon cooling demand the thermostat closes circuit R to Y and G Closing R to...

Page 8: ...oting of the defrost system see Figure 8 The following is a brief outline of the testing of the defrost system 1 Defrost sensor must be closed 32 F or below If temperatures are such that the switch wi...

Page 9: ...air circuit Cleaning should be as often as necessary to keep the coil clean To clean the coil remove the lower access panel and blow out debris by using compressed air or water Be sure power to unit i...

Page 10: ...ASLEEVE 3 Wall Sleeve Kit 45 Louver MHP4 09 12 18 ASLEEVE2 1 2 Wall Sleeve Kit MHP4 09 12 18 24 30MHP4 10 18 24 ASLEEVE2 2 2 Wall Sleeve Kit MHP4 10 30 MHP4 09 36 ASLEEVE6 1 6 Wall Sleeve Kit MHP4 09...

Page 11: ...10 3 10 45 45 1 8 ASLEEVE10 4 10 45 45 1 8 ASLEEVE12 1 12 29 29 1 8 ASLEEVE12 2 12 32 3 4 32 7 8 ASLEEVE12 3 12 45 45 1 8 ASLEEVE12 4 12 45 45 1 8 ASLEEVE 3 45 45 1 8 Thru the wall installations only...

Page 12: ...ITOR RUN CONDENSER FAN COMP CONNECTOR BLOCK BLUE GREY COOLING R G Y O BLACK BLACK X FRmR X FRmC GRAY BROWN C H MH ML FUSE BLUE BLUE COM RVG RV O Y W R DFS2 DFS1 C C DF1 LIGHT BLUE REVERSING VALVE BLAC...

Page 13: ...SEQ C RVG CC O Y W R DFS DFS C TRANSFORMER REVERSING VALVE COIL DF DF DEFROST RELAY FAN MOTOR DUAL CAPACITOR CONTACTOR L1 T1 C R S 208 230V 1 60HZ DEFROST SENSOR DEFROST CONTROL BLOWER CONTROL COM 20...

Page 14: ...LING R G Y O BLACK BLACK X FRmR X FRmC GRAY BROWN C H MH L FUSE BLUE BLUE COM RVG RV O Y W R DFS2 DFS1 C C DF1 LIGHT BLUE REVERSING VALVE BLACK BLACK O O ORANGE WHITE RED BLACK BLACK DEFROST CONTROL B...

Page 15: ...IT SEQ C RVG CC O Y W R DFS DFS C TRANSFORMER REVERSING VALVE COIL DF DF FAN MOTOR DUAL CAPACITOR CONTACTOR L1 T1 C R S 208 230V 1 60HZ DEFROST CONTROL BLOWER CONTROL COM 208 240 24 V G CONTACTOR COIL...

Reviews: