background image

506325-01

Issue 1734

Page 7 of 15

The location of fresh air capable models must conform to 

the requirements of National Fire Protection Association 

NFPA No. 54 in regards to proximity of forced air inlets 

to flue gas terminals. Improper installation could result 

in personal injury or death.

 WARNING

Figure 6. Fresh Air Intake Pipe and Cap

Fresh Air Intake Pipe

Threaded Cap

Thermostat

The room thermostat should be located on an inside 

wall where it will not be subject to drafts, sun exposure, 

or  heat  from  electrical  fixtures  or  appliances.  Follow 

manufacturer’s instructions enclosed with the thermostat 

for general installation procedures. Color-coded insulated 

wires (#18 AWG) should be used to connect the thermostat 

to the unit.

Electrical Connections

All wiring must be done in accordance with the National 

Electrical Code (NEC), ANSI/NFPA No. 70 (latest edition); 

Canadian Electrical Code CSA C22.2 Part 1 (latest edition); 

or local codes, where they prevail. Any alteration of internal 

wiring will void certification and warranty.

Units are factory wired for a 230 volt power supply. If power 

supply is 208 volts, it will be necessary to change a wire 

connection on unit transformer from 240 volt terminal to 

208 volt terminal as shown on the wiring diagram.

Use wiring with a temperature limitation of 75°F minimum. 

Run the 208 or 230 volt, 60 hertz electric power supply 

through a fused disconnect switch to the control box of the 

unit and connect as shown in the wiring diagram located 

on the inside of the control access panel.

The unit must be electrically grounded in accordance with 

local codes or, in the absence of local codes, with the 

National Electrical Code ANSI/NFPA No. 70 (latest edition) 

or CSA C22.2 Part 1 (latest edition).

Operation

Sequence of Operation

Upon initial “power up” to unit, there is a 3-minute time delay 

to the compressor contactor (R to Y). Any 24V interrupt (R, 

C) to the defrost control will initiate the 3-minute delay to 

the contactor.

Cooling

When the thermostat is in the cooling mode, the O circuit 

is powered which energizes the reversing valve. Upon 

cooling demand, the thermostat closes circuit R to Y and 

G. Closing R to Y closes the unit contactor, starting the 

compressor and outdoor fan. The thermostat automatically 

closes R to G circuit which also brings on the indoor 

blower at the same time. Upon satisfying cooling demand, 

the thermostat will open the above circuits and open the 

main contactor, stopping the compressor and outdoor 

fan. The unit is equipped with a time delay; the blower will 

continue to operate for 90 seconds which improves system 

efficiency.

Heating

Upon heating demand, the thermostat closes circuit R to 

Y, which closes the unit contactor, starting the compressor 

and outdoor fan. The reversing valve is not energized in 

the heating mode. The thermostat again automatically 

brings on the indoor fan at the same time. The second 

stage of the thermostat closes circuit R to W, which closes 

the unit sequencers, bringing the auxiliary electric heat on. 

Upon satisfying heating demand, the thermostat opens the 

above circuits and stops unit operation.

NOTE: 

The 7.2 and 10 kW heats strips offer a W1 and 

W2 thermostat connection. Taking advantage of the two 

heat strip circuits requires a 3-stage thermostat (Y for heat 

pump, W1 for electric heat stage 1, and W2 for electric 

heat stage 2). If a 2-stage thermostat is used, “pigtail” W1 

and W2 wires together when connecting the thermostat 

wires at the unit.

Power supply to the unit must be NEC Class 1 and must 

comply with all applicable codes. A fused disconnect switch 

should be field provided for the unit. The switch must be 

separate from all other circuits. If any of the wire supplied 

with the unit must be replaced, replacement wire must be 

of the type shown on the wiring diagram. Electrical wiring 

must be sized to minimum circuit ampacity marked on the 

unit. 

Use copper conductors only

. Each unit must be 

wired with a separate branch circuit and be properly fused.

NOTE: 

Some MHP4 models require two separate power 

supply circuits.  See the unit wiring diagrams and rating 

plates for specifications.

Summary of Contents for MHP-10-24

Page 1: ...est edition in the United States the Canadian Electrical Code Part 1 CSA 22 1 latest edition in Canada and any state or provincial laws or local ordinances Local authorities having jurisdiction should...

Page 2: ...carrier do not install the unit as claim may be denied Check the unit rating plate to confirm specifications are as ordered Table 1 Application Limitations Outdoor Ambient Air Temperature F Minimum D...

Page 3: ...the unit is the preferred method of providing access The door or access panel must be at least 30 wide centered on the unit and as tall as the unit If a return duct is not installed in order to provi...

Page 4: ...nd the louver grille kit along with Figure 2 for guidance in assembling and installing the wall sleeve and louver grille The sleeve is not intended as the sole support for the unit An additional suppo...

Page 5: ...ecommended that supply and return duct connections at the unit be made with flexible joints If flexible ducts are used a 6 sheet metal starter collar is required The supply and return air duct systems...

Page 6: ...inches MHP 18 288 square inches MHP 24 384 square inches MHP 30 36 480 square inches 9 and 10 EER Models Condensate Drain Provisions must be made to properly drain the indoor and outdoor drain pans o...

Page 7: ...e contactor Cooling When the thermostat is in the cooling mode the O circuit is powered which energizes the reversing valve Upon cooling demand the thermostat closes circuit R to Y and G Closing R to...

Page 8: ...oting of the defrost system see Figure 8 The following is a brief outline of the testing of the defrost system 1 Defrost sensor must be closed 32 F or below If temperatures are such that the switch wi...

Page 9: ...air circuit Cleaning should be as often as necessary to keep the coil clean To clean the coil remove the lower access panel and blow out debris by using compressed air or water Be sure power to unit i...

Page 10: ...ASLEEVE 3 Wall Sleeve Kit 45 Louver MHP4 09 12 18 ASLEEVE2 1 2 Wall Sleeve Kit MHP4 09 12 18 24 30MHP4 10 18 24 ASLEEVE2 2 2 Wall Sleeve Kit MHP4 10 30 MHP4 09 36 ASLEEVE6 1 6 Wall Sleeve Kit MHP4 09...

Page 11: ...10 3 10 45 45 1 8 ASLEEVE10 4 10 45 45 1 8 ASLEEVE12 1 12 29 29 1 8 ASLEEVE12 2 12 32 3 4 32 7 8 ASLEEVE12 3 12 45 45 1 8 ASLEEVE12 4 12 45 45 1 8 ASLEEVE 3 45 45 1 8 Thru the wall installations only...

Page 12: ...ITOR RUN CONDENSER FAN COMP CONNECTOR BLOCK BLUE GREY COOLING R G Y O BLACK BLACK X FRmR X FRmC GRAY BROWN C H MH ML FUSE BLUE BLUE COM RVG RV O Y W R DFS2 DFS1 C C DF1 LIGHT BLUE REVERSING VALVE BLAC...

Page 13: ...SEQ C RVG CC O Y W R DFS DFS C TRANSFORMER REVERSING VALVE COIL DF DF DEFROST RELAY FAN MOTOR DUAL CAPACITOR CONTACTOR L1 T1 C R S 208 230V 1 60HZ DEFROST SENSOR DEFROST CONTROL BLOWER CONTROL COM 20...

Page 14: ...LING R G Y O BLACK BLACK X FRmR X FRmC GRAY BROWN C H MH L FUSE BLUE BLUE COM RVG RV O Y W R DFS2 DFS1 C C DF1 LIGHT BLUE REVERSING VALVE BLACK BLACK O O ORANGE WHITE RED BLACK BLACK DEFROST CONTROL B...

Page 15: ...IT SEQ C RVG CC O Y W R DFS DFS C TRANSFORMER REVERSING VALVE COIL DF DF FAN MOTOR DUAL CAPACITOR CONTACTOR L1 T1 C R S 208 230V 1 60HZ DEFROST CONTROL BLOWER CONTROL COM 208 240 24 V G CONTACTOR COIL...

Reviews: