background image

506325-01

Issue 1734

Page 9 of 15

Maintenance

Disconnect all electrical power to the unit before 

conducting any maintenance procedures. Failure to 

disconnect the power could result in personal injury or 

death.

 WARNING

Periodic inspection and maintenance normally consists of 

changing or cleaning filters and (under some conditions) 

cleaning the coils.

Filter

Inspect the filter once a month. Replace disposable filter or 

clean the washable filter as necessary (a minimum of three 

times each heating or cooling season is recommended). 

Do  not  replace  washable  filter  with  a  disposable  filter 

unless  an  installation  was  made  in  which  the  filter  was 

mounted exterior to the unit.

Motors

The indoor and outdoor fan motors are permanently 

lubricated and require no maintenance.

Outdoor Coil

Foreign material should not be allowed to accumulate on 

the outdoor coil surface or other parts in the air circuit. 

Cleaning should be as often as necessary to keep the coil 

clean. To clean the coil, remove the lower access panel 

and blow out debris by using compressed air or water. 

Be 

sure power to unit is shut off before using water to 

clean the coil.

Care should be used when cleaning the coils so that 

the coil fins are not damaged.

Outdoor Base Drain

Foreign material should not be allowed to clog the drain 

hole. Inspect and clear drain opening prior to heating 

season.

System Performance

For maximum performance of this electric cooling system, 

the operating temperatures and pressures should be 

checked and superheat determined at Standard ARI test 

conditions of 82°F outdoor – 80°F indoor dry bulb/67°F 

wet bulb. If superheat measured deviates from the values 

given in Table 5, refrigerant charge should be adjusted 

accordingly for maximum performance.

Table 5. Suction Superheat

Magic-Pak 

Model 

Suction Superheat @ ARI Conditions 

82° OD 80° IDDB/67° IDWB

MHP4-09-12

15-18

MHP4-09-18

9-11

MHP4-09-24

17-19

MHP4-09-30

11-13

MHP4-09-36

23-25

MHP4-10-18

8-10

MHP4-10-24

16-18

MHP4-10-30

24-26

Summary of Contents for MHP-10-24

Page 1: ...est edition in the United States the Canadian Electrical Code Part 1 CSA 22 1 latest edition in Canada and any state or provincial laws or local ordinances Local authorities having jurisdiction should...

Page 2: ...carrier do not install the unit as claim may be denied Check the unit rating plate to confirm specifications are as ordered Table 1 Application Limitations Outdoor Ambient Air Temperature F Minimum D...

Page 3: ...the unit is the preferred method of providing access The door or access panel must be at least 30 wide centered on the unit and as tall as the unit If a return duct is not installed in order to provi...

Page 4: ...nd the louver grille kit along with Figure 2 for guidance in assembling and installing the wall sleeve and louver grille The sleeve is not intended as the sole support for the unit An additional suppo...

Page 5: ...ecommended that supply and return duct connections at the unit be made with flexible joints If flexible ducts are used a 6 sheet metal starter collar is required The supply and return air duct systems...

Page 6: ...inches MHP 18 288 square inches MHP 24 384 square inches MHP 30 36 480 square inches 9 and 10 EER Models Condensate Drain Provisions must be made to properly drain the indoor and outdoor drain pans o...

Page 7: ...e contactor Cooling When the thermostat is in the cooling mode the O circuit is powered which energizes the reversing valve Upon cooling demand the thermostat closes circuit R to Y and G Closing R to...

Page 8: ...oting of the defrost system see Figure 8 The following is a brief outline of the testing of the defrost system 1 Defrost sensor must be closed 32 F or below If temperatures are such that the switch wi...

Page 9: ...air circuit Cleaning should be as often as necessary to keep the coil clean To clean the coil remove the lower access panel and blow out debris by using compressed air or water Be sure power to unit i...

Page 10: ...ASLEEVE 3 Wall Sleeve Kit 45 Louver MHP4 09 12 18 ASLEEVE2 1 2 Wall Sleeve Kit MHP4 09 12 18 24 30MHP4 10 18 24 ASLEEVE2 2 2 Wall Sleeve Kit MHP4 10 30 MHP4 09 36 ASLEEVE6 1 6 Wall Sleeve Kit MHP4 09...

Page 11: ...10 3 10 45 45 1 8 ASLEEVE10 4 10 45 45 1 8 ASLEEVE12 1 12 29 29 1 8 ASLEEVE12 2 12 32 3 4 32 7 8 ASLEEVE12 3 12 45 45 1 8 ASLEEVE12 4 12 45 45 1 8 ASLEEVE 3 45 45 1 8 Thru the wall installations only...

Page 12: ...ITOR RUN CONDENSER FAN COMP CONNECTOR BLOCK BLUE GREY COOLING R G Y O BLACK BLACK X FRmR X FRmC GRAY BROWN C H MH ML FUSE BLUE BLUE COM RVG RV O Y W R DFS2 DFS1 C C DF1 LIGHT BLUE REVERSING VALVE BLAC...

Page 13: ...SEQ C RVG CC O Y W R DFS DFS C TRANSFORMER REVERSING VALVE COIL DF DF DEFROST RELAY FAN MOTOR DUAL CAPACITOR CONTACTOR L1 T1 C R S 208 230V 1 60HZ DEFROST SENSOR DEFROST CONTROL BLOWER CONTROL COM 20...

Page 14: ...LING R G Y O BLACK BLACK X FRmR X FRmC GRAY BROWN C H MH L FUSE BLUE BLUE COM RVG RV O Y W R DFS2 DFS1 C C DF1 LIGHT BLUE REVERSING VALVE BLACK BLACK O O ORANGE WHITE RED BLACK BLACK DEFROST CONTROL B...

Page 15: ...IT SEQ C RVG CC O Y W R DFS DFS C TRANSFORMER REVERSING VALVE COIL DF DF FAN MOTOR DUAL CAPACITOR CONTACTOR L1 T1 C R S 208 230V 1 60HZ DEFROST CONTROL BLOWER CONTROL COM 208 240 24 V G CONTACTOR COIL...

Reviews: