    HPV1000-App_Note_27 

                   

  

 

 

Closed Loop Start Guide 

 
 

 

Encoder Wiring 

 
3)  The encoder should be wired to the drive as follows: 

 

Table 1 CL: PG-X3 Encoder connections

 

 

IP is the +VDC, and IG as the common. 

 

The encoder voltage is selected via the jumper CN3 as either 5.5V or 12V 

 

Note that the encoder is wired in to the upper case terminals. The lower case terminals are an output 
from the drive 

and won’t necessarily be used. 

 

If wired single ended, PG Card Detect (F1-20) must be Disabled 

 
Hoistway Parameter Set-up 

 
4)  Enter / verify the following parameters: 

 

CONTRACT CAR SPD (O1-25) 

parameter should be the lift contract speed in m/s. This can be verified 

with a hand tachometer if required and adjusted if required. 

 

CONTRACT MTR SPD (O1-26) 

parameter should be set to the RPM that is required to make the lift travel 

at contract car speed 
 

NOTE:

  The above two parameters are utilised by the drive for many purposes regarding speed control of the lift, 

therefore its important these are set correctly prior to continuing any further.

 

 
Input Voltage 

 
5)  Enter the Line Voltage: 

 

INPUT VOLTAGE (E1-01) parameter should be set to the measured incoming phase to phase 
voltage. 

 
 
 
 
 