Chapter 13.0: Special Applications and Field Instructions
13.1: Field Cutting of Conductor Bar Sections
13.1.(a):
Cut ends squarely with metal cutting band saw or hack saw.
13.1.(b):
If cut conductor section is to be joined with another conductor section, cut insulating
cover back 1” from end of conductor. Leave insulating cover flush with end of conductor if
transfer cap is to be installed.
13.1.(c):
Drill ends of cut conductors as follows:
•
For 90 Amp conductors, use 19/64” drill.
•
For 110, 250 and 350 Amp conductors, use ¼” drill.
•
For transfer caps, use 19/64” drill.
13.1.(d):
De-burr ends of conductors.