8.2.(f):
Verify the end face of each line element is together.
8.2.(g):
Tighten the other nut of the joint assembly 55 in-lb.
8.2.(h):
Assemble power feed wire to one lug of the power feed assembly, using an appropriate
terminal connector. Feed power feed wire through end of power feed cover before attaching the
power feed cover to the joint.
8.2.(i):
Assemble nut to lug and tighten to a maximum of 55 in-lb.
8.2.(j):
Assemble the power feed cover over the power feed. Reference the joint cover
instructions.
NOTE: Tools Required: 3/8” Wrench or Socket
NOTE: A liberal coating of joint compound, FS-JNJC, is recommended on all mating faces that conduct
current.
NOTE: To use the in-line power feed as an end-line power feed assembly, see page 28 for instructions.