5.1.2 Reference Limits
These parameters will limit the frequency range as a percentage of maximum output frequency (E01.04).
An alternate upper limit frequency can be used during operation when a Multi-Function Digital Input (MFDI) is set to
59 (Alt F-Ref UpLimit) and the MFDI is on. Alternate Upper Limit Frequency = (B02.04) % x (E01.04).
Figure 5-1: Setting Frequency Upper and Lower Limits
Parameter Name
Function
Range
Default
B02.01
Frequency Reference
Upper Limit
Sets as a percentage of the maximum output frequency
(E01.04), the maximum frequency at which the VFD is
able to run.
0.0–110%
100.0
B02.02
Frequency Reference
Lower Limit
Sets as a percentage of the maximum output frequency
(E01.04), the minimum master frequency reference
only.
0.0–110%
0.0
B02.03
Reference 1
Lower limit
Sets as a percentage of the maximum output frequency
(E01.04), and determines the minimum frequency the
VFD is able to run when an analog signal is below this
level.
0.0–110%
2.0*
B02.04
Alt Upper Limit
Alternate of B02.01 set by H01.xx = 59.
0-110%
100.0
Internal
Frequency
Reference
B02.02 x (E01.04)
E01.04
100% (E01.04)
HZ
0
Set Frequency Reference
B02.01 x (E01.04)
or B02.04 x (E01.04)