IMPULSE
®
•G+ Mini Technical Manual
November 2020
Page 71
Figure 5-18: Load Check
C05.22
LC Zone 14
Current/Torque for Zone 14
000–250%
000
C05.23
LC Zone 15
Current/Torque for Zone 15
000–250%
000
C05.24
LC Zone 16
Current/Torque for Zone 16
000–250%
000
C05.25
LC Integral Time
Integral time used to smooth transitions
0.00–2.55 sec
0.05
C05.26
LC Delay Time
Load Check delay time for transitions
0.00–2.55 sec
0.25
C05.27
LC Rev Dir Delay
Minimum delay between Reverse to
Forward transition after Reverse
frequency exceeds C05.28
0.00–2.55 sec
0.00
C05.28
LC Rev Dir Freq
Minimum frequency that will trigger the
C05.27 delay
0.0–60.0 Hz
30.0
Parameter
Name
Function
Range
Default
Frequency
Output
Run
Command
C05.03
C05.04
Freq Reference
C05.09
C05.10
C05.11
Summary of Contents for IMPULSE G+ Mini
Page 15: ...IMPULSE G Mini Technical Manual November 2020 Page 15 Figure 2 1 Long Time Storage...
Page 18: ...IMPULSE G Mini Technical Manual November 2020 Page 18 Figure 2 4 Diagram C...
Page 181: ......
Page 182: ...IMPULSE G Mini Adjustable Frequency Crane Controls Technical Manual November 2020...