IMPULSE
®
•G+ Mini Technical Manual
November 2020
Page 122
Table 5-16: OLV Stabilization Table
NOTE:
If the motor is hunting, increase the value of N02.05 per the table to stabilize the load.
5.8.2 Online Tuning
Control Method
(A01.02)
OLV Stabilization Level
(N02.05)
Torq. Comp Time
(D03.02)
AFR Time
(N02.02)
Independent setting of
D03.02 & N02.02
2 (OLV)
00 (default)
20
50
No
01
25
63
No
02
30
75
No
03
35
88
No
04
40
100
No
05
45
113
No
06
50
125
No
07
55
138
No
08
60
150
No
09
65
163
No
0A
70
175
No
0B
75
188
No
0C
80
200
No
0D
85
213
No
0E
90
225
No
0F
95
238
No
10
100
250
No
11
105
263
No
FF
Note 1
Note 1
Yes
NOTE 1:
If N02.05 = FF, the values that were in D03.02 & N02.02 will be retained.
When N02.05 = FF, use the following equation to determine the new N02.02 value:
Parameter
Name
Function
Range
Default
N06.01
Line-to-Line Motor Tuning Selection
Line-to-Line Motor Tuning
00–01
01
00 Disabled
01 Enabled
CAUTION
Increasing the value of N02.05 too high may result in the motor not developing enough torque to lift the load.