Page 125
5.9.2 Keypad Key Selection
O01.03
Display Scaling
Units for parameters and monitor
related to frequency reference and
output frequency can be scaled as
shown below
00–03
00
00 0.01 Hz
01 0.01%
02 r/min
03 User-set
O01.10
User-set Display Maximum Units
Sets maximum when operating at
maximum output frequency
00000–
60000
06000
O01.11
User-set Display Decimal
Sets user display decimal point
00–03
02
00 No Decimal Point
01 01
02 0.01
03 0.001
Parameter
Name
Function
Range
Default
O02.01
Local/Remote Key
Sets Local/Remote Key Operation
00–01
00
00 Disable
01 Enable
O02.02
Stop Key Operation
Sets Stop key Operation
00–02
00
00 Coast to Stop
01 Decel to Stop
02 Use B03.03 Stopping Method
O02.03
User Defaults
Sets/Clears User Defaults
00–02
00
00 No Change
01 Set Defaults
02 Clear All
O02.04
kVA Selection
Determines the model number of the VFD,
which is based on the kVA rating. The
following are Magnetek model numbers.
*Initial value determined by VFD model.
61-9D
*
61 2A0002
2001-G+M
62 2A0004
2003-G+M
63 2A0006
2005-G+M
65 2A0010
2008-G+M
66 2A0012
2011-G+M
68 2A0020
2017-G+M
6A 2A0030
2025-G+M
6B 2A0040
2033-G+M
Parameter
Name
Function
Range
Default