5.2.5 Phantom Stop
The Phantom Stop feature is designed to stop operation using the stopping method selected in C03.09 when a
Phantom Fault input (H01.01–H01.07 = 5F or 63) is active. The VFD will indicate a Phantom Fault has occurred by
blinking the LED on the RUN key in sequence of two short bursts. The VFD will resume normal operation when a
Phantom Fault is removed.
5.2.6 Klixon Action
The Klixon digital input is intended for motors that have a Motor Thermal Overload Switch called a Klixon. The
Klixon is usually embedded in the motor windings, and changes state when the motor reaches a certain
temperature. When a digital input (H01.01~H01.07 = 56 or 57) is active, the VFD will use the stopping method
programmed in C03.11 and display the oL8 Klixon alarm. The VFD will resume normal operation when the motor
cools down and the input changes state for normal operation.
Parameter
Name
Function
Range
Default
C03.09
Phantom Stop Selection
Stopping Method when H01.01–H01.07 =
5F or 63 (Phantom Fault)
00–02
01
00 Decel to Stop
01 Coast to Stop
02 Use B03.03 Method
Parameter
Name
Function
Range
Default
C03.11
Klixon Action
Stopping Method when H01.01–H01.07 = 56
or 57
00–01
00
00 Use B03.03 Method
01 Allow Lower Only