Pedestrian Barrier High Door MPH 112
Start-up and operation
5817,5005EN / Version 01
73
11.4 Program mode MPH
Default setting fort he pedestrian barrier MPH is the program mode
MPH. This one is set by the factory via the DIP switches S2.1 and
S2.2. In this program mode the light barriers and the safety light
barriers initiate the opening and the closing of the glass wings and
realise unauthorized access attempts.
The light barriers 1 and 2 as well as 5 and 6 fulfil the following
function:
opening of the glass wings if a person enters the freed side
serve to detect the direction and
detect unauthorized access attempts.
The safety light barriers 3A and 3B as well as 4A and 4B fulfil the
following function:
safety monitoring
close glass wings if a person passed both light barriers.
Mag00022a
Master
Slave
GED
GED
LS
1
LS
2
LS
6
LS
5
LS
3A
/
LS
3B
LS
4A
/
LS
4B
Fig. 26: Function of the light barriers