Full Height Turnstile MPT-152
Electrical connection
45
6.5 Relay outputs X1
Isolated relay contacts, wired in groups
Switched voltage 5 - 24V
Switched current 10 mA – 1 A
Relay output
Function
Description
R1
Global error / Power failure
When certain errors occur, a permanent signal is deliv-
ered via this output for as long as the error is present.
Potential error/alarm states are:
1
Barrier runtime too long = obstacle detected
2
CAN communication with end stage is impaired
3
Hardware error in end stage
4
Software error in end stage
5
Homing function running
6
Emergency input is activated
(inverted signal no longer present)
7 Power
failure
8
Manual reset expected (only if fitted)
R2
Full height turnstile in
blocked position
A permanent signal is delivered via this output for as long
as the full height turnstile is in one of the three rest posi-
tions.
R3 Display
passage
Clear left
A permanent signal is delivered via this output for as long
as the passage to the left is clear.
R4 Display
passage
Clear right
A permanent signal is delivered via this output for as long
as the passage to the right is clear.
R5
Counting pulse left
A counting pulse lasting 500 ms is delivered via this out-
put at the start of the passage.
R6
Counting pulse right
A counting pulse lasting 500 ms is delivered via this out-
put at the start of the passage.
Table 6: Relay outputs