Full Height Turnstile MPT-152
Maintenance
55
9.3 Maintenance
schedule
The following describes the maintenance work that is necessary for
optimal, trouble-free operation.
If increased wear of individual components or functional groups is
revealed during regular inspections, the operator must reduce the
required maintenance intervals on the basis of the actual signs of
wear.
In case of queries regarding the maintenance work and intervals,
contact the manufacturer (service address, see Page 2).
Interval
Maintenance work
To be carried out by
Every 6 months
Check the centre column and side components for
damage.
Expert
Visual inspection of the support beam, inside and
out, for damage. Clean the housing and repair paint
damage as necessary.
Expert
Check the optional lock unit
Expert
Check play on the floor bearing and ease of move-
ment
Expert
Check screwed connections on the drive flange
Expert
Check function of the residual current operated de-
vice
Qualified electrician
Every 12 months
Check electric cables for damages.
Qualified electrician
Check if all electrical connections are firm.
Qualified electrician
Check signs and labels for legibility.
Expert
Check foundation fastening.
Expert
The electrical tests are to be performed in accordance with the regulations applicable at the installation
site.
Table 9: Maintenance schedule