1.4  System menu – Installation specific Settings 

In the system menu all installation specific settings can be made. 

 

Display

 

Menu Item 

Setting 

1234

 

Normal Operation 

M long 

 Display 

SYS

  = System menu 

 

Alternating shows program version; for 

example A02 

S oc

   

1234 

Alternating

 

Switch threshold 

0...9999

 

 

HYS       

 

1234 

Alternating

 

Count hysteresis 

1...250

 

 

M short 

 next menu item 

SkP~       

 

1234 

Alternating

 

Upper Count 

threshold 

0...9999

 

 

SkP_       

 

-123 

Alternating

 

Lower Count threshold 

0...-999

 

 or 

   

 change 

M long 

 save 

inP1

 ...

Alternating

 

 Add 

 Sub 

 rEs 

 no.F 

Input functions 

• 

Increment count 

• 

Decrement count 

• 

Reset count 

• 

No function 

 

 
 

Two buttons simultaneously 

M long 

End

  = back in normal operation 

rEL 

Alternating

 

 oc.on 

 Fr.on 

 Output function  

 

• 

Normally closed 

• 

Normally open 

 

LoPo 

Alternating

 

 off 

 on 

Power Save Mode 

• 

off (Display an) 

an (Display aus) 

 

Pork 

Serial Interface 

 

 

Summary of Contents for VEK CN1

Page 1: ...1 1 Operating Instructions DIGITAL COUNTER VEK CN1 Version 2002_03...

Page 2: ...g instructions and on any alterations and extensions that may be relevant Please read these operation instructions prior to installing the equipment COPYRIGHT 2001 Magnetic Automation Corp All rights...

Page 3: ...____________________7 1 4 System menu Installation specific Settings ________________________________________ 8 1 4 1 Operating Modes Switching point __________________________________________________...

Page 4: ...4 digit display Totalize counter 999 bis 9999 4 noise immunity inputs each function Reset individually adjustable 1 Reset input optional 1 Relay output 250V 5A for Traffic lights and Lot Full signs o...

Page 5: ...ount must be checked and if necessary updated Display Status Setting 1234 Flashing Return after loss of power or Update open space count M Confirm existing count is correct 1 2 3 Display during normal...

Page 6: ...ormal Operation or First digit flashing modify counter 1234 One digit flashing Modify Counter or Digit 1 or 1 sec Fast scroll or 3 sec 10 s 100 s 1000 s M short 100 s 10 s 1 s Cancel M long Skor saved...

Page 7: ...eset Input counter M short Cancel reset Note 1 The open space or quantity of passed vehicles count will not be effected during reset of any of the input counts 3 If one of the four 4 input counter dis...

Page 8: ...ng Count hysteresis 1 250 M short next menu item SkP 1234 Alternating Upper Count threshold 0 9999 SkP_ 123 Alternating Lower Count threshold 0 999 or change M long save inP1 4 Alternating Add Sub rEs...

Page 9: ...relay will be released as soon the count reached the adjusted count hysteresis 1 4 1 2 Operating Mode PASSING VEHICLE COUNT The PASSING VEHICLE COUNT is preferably used when the control audit count of...

Page 10: ...he default is 9999 for the upper and 999 for the lover level Display Status Setting 1234 Normal Operation M long S S S oc M 2 x short SkP upper level 0 9999 M short SkP_ lover level 999 0 SkP _ 1234 A...

Page 11: ...nge Function no F rEs Sub Add Add Sub rEs no F M short Cancel M long Skor save Factory default is Incrementing for Input 1 and 3 and decrementing for Input 2 and 4 1 4 5 Output settings The output rel...

Page 12: ...to factory default using following procedure Display Status Setting Turn off power to the unit for longer then 2 seconds 1234 Flashing Return after power failure Press two buttons simultaneously Err...

Page 13: ...he control boards please use electrostatic save measurements to prevent any damage to the components Do not touch the board or any of the components Internal supply is does not use the External supply...

Page 14: ...Using one of the inputs as count reset input all counts can be reset to 0 when a signal is applied According to the relay output setting the relay switches to OPEN or OCCUPIED The reset does not effec...

Page 15: ...C Storage Temperature 40 C to 70 C Humidity max 95 non condensing Count Total 999 bis 9 999 Per count input up to 9 999 9999 Inputs Opto Coupled 4 Inputs Minimum input time 50ms Input current 5mA at 1...

Reviews: