Control unit MGC mTripod
Corrective action
8.6
Event, warning and error messages (troubleshooting)
8.6.1
Event, warning and error messages – Logic control (control unit)
Number
Designation
Possible cause
Corrective action
3120
ERROR
Mains power failure
Short-term power
failure detected.
Check supply voltage and
mains quality.
5112
WARNING
24 V logic voltage too
low
Under voltage
›
Reduce load.
›
Check mains unit.
5530
ERROR
EEPROM checksum
Checksum of
parameters not correct.
›
Reset parameters to
factory settings.
6000
ERROR
Module SW-update
failed
Firmware update was
not performed correctly.
›
Restart the control unit.
›
If the error remains,
perform the update again
via the service module.
6101
ERROR
Software error: VS
Software error
›
Perform software update.
6102
ERROR
Software error: System
bus
Within the control, an
error is pending in
communication.
›
Check SW versions of all
plug-in modules. If
necessary, update via the
service module.
›
If all FW versions are up to
date, contact service.
6103
WARNING
FW defaults restored
After a software update.
›
Perform reset.
›
If the error occurs
repeatedly, replace the
control unit MGC.
6104
WARNING
Unexpected motor state Motor control error
›
Perform reset.
›
Perform software update.
›
Check wiring.
6105
ERROR
Homing failed
The pedestrian gate
could not execute a
reference run.
›
Check motor
communication.
›
Check mechanics.
›
Check the homing sensor.
›
Perform reset.